Permit Number: T08CM00744
Parcel: 13821024B

Address:
211 W CORONA RD

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM00744
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2008 GERRY KOZIOL WWM REVIEW Approved
03/31/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4/01/08
Activity: T08CM00744
Address: 211 W Corona Rd.
Applicant: Karen Merodias

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:
4. Provide last approved site plan for verification of Arizona room approval.

STRUCTURAL PLANS:
5. Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the floor plans. Note the requirement for a deferred submittal if the truss calculations will not be submitted with the plan review.

ELEVATIONS:
6. Specify two-layer underlayment for low-slope (2:12 to 4:12) asphalt shingle roofs, R905.2.7.

SECTIONS - DETAILS:
7. Provide uplift resistance for roof framing, R802.11.1.

ELECTRICAL PLAN:
8. Provide an electrical riser diagram with grounding method and bonding to metallic piping, E3303, E3507. Show an underground service entrance on the Riser Diagram or complete the Underground Electrical Service Wavier form
9. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11.
10. Bedroom outlets shall be protected by combination type arc-fault interrupters (receptacles, lights, and smoke detectors), E3802.12.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review