Permit Number: T08CM00702
Parcel: 11506185C

Address:
175 W PLATA ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM00702
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2009 MARTIN BROWN FIRE REVIEW Needs Review
03/13/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. At the marked crossing:
a. Angle crossing directly to both accessible route at the curb corners.
b. Provide ramps or otherwise modify 6" curb line at both ends of crossing
c. Provide detectable warnings at both ends of marked crossings as per ANSI 117.1 Sections 406.12 and .14.
2. provide slopes of new concrete accessible route at Nortth elevation of building and the existing concrete accessible route between the new and existing buildings.
03/16/2009 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM00702
175 W. Plata St.
Site Plan - Commercial Storage

TRANSMITTAL DATE: 03/13/09

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.2 Provide the legal description of the property on the site plan.

2. DS 2-02.2.1.5 Provide the distance and bearings of all property lines.

3. DS 2-02.2.1.6 Provide dimensions for the footprints of all structures.

A "Family Dwelling" use is allowed in the I-1 zone as a secondary use and only as a caretaker use for the principal use. See LUC Sec. 2.7.2.4.A and subject to Sec. 3.5.7.7. Review and revise plans. Parking spaces are required to be included in the parking calculations as well as the secondary use is to be listed with the uses.

Provide on the footprint of all structures the height of all existing and proposed structures.

4. DS 2-02.2.1.7 Provide the required zoning setbacks distances from property lines and distances between buildings.

5. DS 2-02.2.1.4 A small, project-location map shall be drawn on the first sheet of the development plan, preferably in the upper right corner. The map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information.

1. Section, township, and range; section corners; north arrow; and the scale will be labeled.

6. DS 2-02.2.1.8 Handicap parking space is dimensioned at 11' width but note indicates 9' width. Clarify.

Clearly indicate the location of the wheel stop curbing with dimension. Minimum 2'-6" from front of parking space to the front of the wheel stop curb.

Clearly indicate the correct number of required parking spaces in the calculations. The caretakers quarters will require 2 parking spaces.

7. DS 2-02.2.1.9 Provide in the calculations the number of required and provide bicycle parking spaces. See LUC Sec. 3.3.4 and DS 2-09 for requirements.

Please provide a dimensioned detail class 2 bicycle parking spaces and a detail of the type of rack proposed. Be aware that that development standard 2-09 has been revised.

Please provide a plan view detail of the proposed class 2 bicycle parking spaces. Single rack spaces placed in a row will allow a minimum of seventy -two (72) inch length per bicycle parking space and a minimum of thirty (30) inches between outer spaces of racks. A five (5) foot wide access aisle measured from the front or rear of the seventy-two (72) inch long parking space will be provided beside each row. Lighting will be provided such that all facilities are thoroughly illuminated and visible from adjacent sidewalks, parking lots, or buildings, during working hours. The surface of the facility can be surfaced the same as for motor vehicle parking or with a minimum of one (1) inch thickness of one-fourth (1/4) inch aggregate material.

Class 2 bicycle parking facilities will be located no more than fifty (50) feet from the main building entrance(s) and will be along the front side of the building as well as along other sides of the building that has an entrance. Bicycle access through the development will be separate from the pedestrian ways. Vehicular access may be used as bicycle access. Bicycle access to a parking facility may cross a pedestrian way at a right angle (DS2-09.3.2).

Please review the revised DS 2-09 and provide the necessary corrections to the bicycle parking as required. Once changes are provided and reviewed further comments may result. The revised DS may be found on the web at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/DevStd209.pdf

8. DS 2-02.2.1.10 Provide sight visibility triangles for the entrance from the north side of the property.

Sight visibility triangles do not appear to be the correct size. See engineering comments.

9. DS 2-02.2.1.11 Near the north east side of the property along the east side of the PAAL a 2' shy area is required. Provide curbing along this side of the PAAL to prevent vehicles from driving onto unimproved portions of the site.

The entrance to the trash enclosure will require curbing or barriers to prevent vehicles from driving onto unimproved portions of the site.

10. DS 2-02.2.1.12 Clearly indicate the required physical separation of the sidewalk from a vehicle use area along the east side of the eastern most parking space.

11. DS 2-02.2.1.13 If applicable, provide location, type, size, and height of existing and proposed signage.

12. DS 2-02.2.1.14 Provide dimensioned location of the required loading zone. Provide in the calculations the number of required and provided loading zones including required size. Per LUC Sec. 3.4.5.2 , one 12X55 loading zone is required.

13. DS 2-02.2.1.20 If applicable, provide the location and use of all easements of record together with recording docket and page reference.

14. DS 2-02.2.1.25 If applicable, provide existing and proposed lighting layout and type.

15. DS 2-02.2.1.31 Provide the proposed use as follows: Commercial Storage "34", subject to: Sec. 3.5.10.1 and Family Dwelling , Secondary Land Use subject to: Sec. 3.5.7.7.

16. DS 2-02.2.2.3 Provide the allowed and proposed Floor Area Ratio (FAR) in the calculation portion of this site plan.

17. Add a note stating that the existing gates at both entrances are to remain open during business hours.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM00702.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/20/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: March 20, 2009
SUBJECT: Site Plan
TO: Troy Williams
LOCATION: 175 W Plata Street, T14S, R13E, Section 1, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM00702 (First Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan.

Site Plan:

1. Please provide project address per D.S. 2-02.2.1.3.
A. D.S. 2-02.2.1.4. Revise location map to cover approximately one (1) square mile and draw at a minimum scale of 3" = 1mile, and provide the following information:
1. Show the subject property approximately centered within the one (1) square mile area.
2. Identify conditions within the square mile area, such as major streets and watercourses.
3. Section, Township, and range; section corners; north arrow; and scale will be labeled.
2. Please label lot bearings per D.S. 2-02.2.1.5
3. Clearly indicate new proposed storage building, label as Proposed new storage building per D.S. 2-02.2.1.6.
4. Label all applicable existing and future sight visibility triangles per D.S. 2-02.2.1.10.

5. Label all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
6. DS Sec.2-02.2.1.A.11: Revise the site plan to show the minimum 12-foot separation that is required between adjacent driveways. Show and label the existing driveways adjacent to the site and verify the 12-foot minimum width. Refer to Tucson Code (TC) Chapter 25-39 for curb cut and driveway requirements. Call out distance to adjacent driveways.
7. Call out all curb radii's on site plans.
8. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. Refer to AASHTO for the national standards for turning radii.
9. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
10. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
11. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. Provide roof drainage and provide a detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage. At pedestrian sidewalks is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.
12. D.S. Sec.2-02.2.1.17: It appears that cut and fill will not be occurring for the proposed patio. However, as part of the site submittal requirement estimated cut and fill quantities are required to be indicated on the plans so that it is clear to the inspector that no cut in fill is to be taking place. If not cut and fill is taking place indicate the quantity of zero (0) on the plan. Estimated cut and Fill: Cut = 0 and Fill = 0 will suffice.
13. Please show dimensioned existing and future right-of-way and label per D.S. 2-02.2.1.19.
14. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for 10th Avenue and Plata Street.
15. Verify that all easement of record have been graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
16. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
17. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. Provide contour interval on plan.

18. Verify that all fences, walls, or vegetation for screening and sight visibility are identified by type, material, height, location and spacing per D.S. 2-02.2.1.27.
19. Verify that the refuse container detail is in accordance with the included Solid Waste Detail. Specifically ensure that the inside dimensions are indicated per D.S. 2-02.2.1.32 and D.S. 6-01.0.
20. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location. Current location of trash area will need to be approved by Environmental Services, Andy Vera. Provide email or letter from Andy Vera approval of location.
21. Clarify is approach to trash enclosure labeled 2" black top is to include 4" A.B.C for refuse vehicle. Current 2" back top cannot be approved.
22. Get approval for gate from Environmental Services, access to refuse container appears to be of concern.
23. Be advised that a permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
24. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
25. List contact name for the consulting engineer and contact name and phone number for the owner on the plans.
26. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
27. All symbols on plans need to be indicated in legend. Indicate all symbols in legend.
28. If cut and fill quantities add up to 50 cy a grading plan will be required for this project. If applicable submit 3 sets of grading plans, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".
29. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
03/27/2009 JOE LINVILLE NPPO REVIEW Denied See landscape comments.
03/27/2009 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The vehicular use area must be provided with post barricades or wheel stop curbing designed to prevent parked vehicles from extending beyond the property lines; damaging adjacent landscaping, walls, or buildings and to prevent vehicles from driving onto unimproved portions of the site.
per DS 3-05.2.3.C. Revise the plans in the vicinity of the dumpster access area as necessary.

2) Dimension the length and width of landscape borders on the landscape plan per DS 2-07.2.2.A.2.f.

3) The area between the right-of-way line and the curb, if not covered with vegetation, shall be covered with an appropriate inorganic ground cover, such as decomposed granite. Revise the plans to clarify compliance by noting the existing or proposed dust control treatments. LUC 3.7.2.4.A.4

4) Revise the landscape plan to show the ultimate size of plants indicated by the spread of canopy, circumference of shrubs, or spread of ground cover. Use appropriately sized symbols. DS 2-07.2.2.A.1.c

4) The irrigation plan appears to indicate the use of sleeves for almost all of the lines. Clarify the plan and legend if necessary to distinguish between areas where sleeves are proposed and areas where no sleeves are provided.
DS 2-06.5.4.A.3

5) Submit a native plant preservation plan or application for exception. LUC 3.8.4.2

6) Add the Legal description to the landscape plan.
DS 2-07.2.1.B.1

7) Trees and shrubs are to be selected and located so that, at maturity, they do not interfere with existing on-site or off-site utility service lines or utility easements. LUC 3.7.2.6.B
Show utility lines or easements on the landscape plan, if applicable.

8) Revise the landscape plan to locate plants in appropriate planting areas. Currently plants are shown in the sidewalk and driveway areas along Plata Street. DS 2-06.3.8

9) Revise the landscape plan to include the number of individual plants used for screening purposes.
DS 2-07.2.2.A.1.a

10) Revise the landscape plan to provide screening south of the Tenth Avenue ingress/egress location and south of Building 'B'.

11) An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. Provide dimensions on the landscape plan. DS 2-07.2.1.A.1.e
04/07/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the location and size of the public sanitary sewer and
c. the location, invert, and rim elevation of the upstream and downstream manholes.
Reference City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
04/16/2009 SUE REEVES REJECT SHELF Completed