Permit Number: T08CM00683
Parcel: 133147540

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00683
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/13/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM00683 3/5/08

1. Heat Pumps and Fan Coils are new on Electrical. Not new on Mechanical Plans. Coordinate with Mechanical and clarify.
2. Please demonstrate that distance from TEP to electrical service is 100', and that distance from service to new Panel is 150', and rework fault calculations as necessary. THIS COMMENT WAS MADE ON THE INITIAL SUBMITTAL. On scaled drawing distance from service to new panel appears to be only ½ of the 150' noted in the fault calculations.