Permit Number: T08CM00683
Parcel: 133147540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00683
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 STEVE SHIELDS ZONING REVIEW Approved
02/28/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00683 2/29/08

1. Heat Pumps and Fan Coils are new on Electrical. Not new on Mechanical Plans. Coordinate with Mechanical and clarify.
2. Please demonstrate that distance from TEP to electrical service is 100', and that distance from service to new Panel is 150', and rework fault calculations as necessary.
02/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/29/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/29/2008 ROBERT SHERRY WATER REVIEW Approved
02/29/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/29/2008 DAVE MANN FIRE REVIEW Approved
03/05/2008 GERRY KOZIOL WWM REVIEW Approved
03/05/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review