Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00683
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/28/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 02/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00683 2/29/08 1. Heat Pumps and Fan Coils are new on Electrical. Not new on Mechanical Plans. Coordinate with Mechanical and clarify. 2. Please demonstrate that distance from TEP to electrical service is 100', and that distance from service to new Panel is 150', and rework fault calculations as necessary. |
| 02/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/29/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/29/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/29/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/05/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/05/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |