Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00672
Parcel: 12701004C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00672
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
02/28/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00672 2/28/08

1. Provide a circuit for the Water Heater. Reference Sheet P1 Plumbing Fixture Schedule.
2. Lights on Lighting Plan are on LP-1. This is a receptacle circuit according to the Power Plan.
3. On the Power Plan there is a receptacle circuit without panel and circuit designation. Five receptacles, 3 of which are in the lounge, one in the Open Work Area, and one at a modular work station.
02/28/2008 ROBERT SHERRY WATER REVIEW Approved
02/28/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/28/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/28/2008 MARTIN BROWN FIRE REVIEW Approved
02/29/2008 GERRY KOZIOL WWM REVIEW Approved
02/29/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/29/2008 DELMA ROBEY OUT TO CUSTOMER Completed