Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM00668
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/16/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/16/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location of the reduced pressure backflow assembly on the drawings. Reference Section 103.2.3, UPC 2006. |
04/16/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. Also , be advised that separate, deferred submittals for permits will be required through the fire department for installation of fire sprinklers, fire service underground piping, and fire alarms. |
04/24/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Needs Review | |
04/24/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
04/24/2008 | DROBEY1 | ZONING | REVIEW | Needs Review |