Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM00668
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/16/2008 ROBERT SHERRY WATER REVIEW Denied Show the location of the reduced pressure backflow assembly on the drawings. Reference Section 103.2.3, UPC 2006.
04/16/2008 DAVE MANN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Also , be advised that separate, deferred submittals for permits will be required through the fire department for installation of fire sprinklers, fire service underground piping, and fire alarms.
04/24/2008 PAUL MACHADO ENGINEERING REVIEW Needs Review
04/24/2008 DROBEY1 WWM REVIEW Needs Review
04/24/2008 DROBEY1 ZONING REVIEW Needs Review