Permit Number: T08CM00658
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00658
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
02/27/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/27/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/27/2008 ROBERT SHERRY WATER REVIEW Approved
02/27/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/27/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/27/2008 DAVE MANN FIRE REVIEW Approved
02/27/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00658 2/28/08

1. Note on Power Plan calls for the removal and relocation of Panel A. Could not find such new location. Line Diagram insicates that Panel A is "future." Could it be the intent that the contractor is to remove this panel and salvage it to the Owner for such future use? Please clarify.
2. Both AC units are listed on Ckt B-13,15,17.
3. On the Riser Diagram the bonding in the gutter has to be sized according to NEC Table 250.66 because the 3/0 conductors are on the line side of the service disconnecting means. So the #6 CU GND needs to be #4.
4. Fault current note address Panel A as well as Panel B, but Panel A does not appear in the current scope of work.
5. Fault current note calls for Panel B to be series rated, but panel B already exists. Could it be that Panel B is already series rated with its remote upstream overcurrent protective device, and that such series rating shall be maintained between the new fuses and all existing and new breakers?
02/29/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/29/2008 DELMA ROBEY OUT TO CUSTOMER Completed