Permit Number: T08CM00657
Parcel: 112062350

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00657
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2008 MARTIN BROWN FIRE REVIEW Approved
02/27/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/27/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00657 2/27/08

1. MOCP is 35A according to the Packaged Heat Pump Schedule. Please resize circuit breakers or specify fuses of that size in HP disconnects.
2. Minimum font size is 1/8". This effects the panel schedules.
3. Egress lighting appears to be in violation of NEC 700.12 (E).
02/27/2008 ROBERT SHERRY WATER REVIEW Approved
02/27/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/27/2008 PAUL MACHADO ENGINEERING REVIEW Approved
02/27/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/28/2008 CPIERCE1 WWM REVIEW Needs Review
02/28/2008 CPIERCE1 ZONING REVIEW Needs Review
02/28/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review