Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00657
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/27/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/27/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00657 2/27/08 1. MOCP is 35A according to the Packaged Heat Pump Schedule. Please resize circuit breakers or specify fuses of that size in HP disconnects. 2. Minimum font size is 1/8". This effects the panel schedules. 3. Egress lighting appears to be in violation of NEC 700.12 (E). |
| 02/27/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/27/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/27/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 02/27/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/28/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 02/28/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 02/28/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |