Permit Number: T08CM00655
Parcel: 10408078C

Review Status: Completed

Review Details: SITE

Permit Number - T08CM00655
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2008 MARTIN BROWN FIRE REVIEW Approved
03/06/2008 PETER MCLAUGHLIN NPPO REVIEW Approved
03/06/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Some of the parking spaces along with two tree planter areas shown on the approved plan (located near the proposed addition) are being removed on the revised plan. Provide a copy of the last approved landscape plan along with a revised landscape plan showing the new tree planter calculation which takes into account the removal of the parking spaces and any canopy trees.
03/06/2008 SSHIELD1 ADA REVIEW Passed
03/06/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Jim Click Nissan - AutoMall
T08CM00441
Site Plan (1st Review)

TRANSMITTAL DATE: March 6, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance, see comment 5 below. There is not enough information provided on this site plan for a full review. Provide a site plan that meets the minimum requirements of D.S. 2-02.

2. Provide a copy of the site plan that approved the 7th ADDITION, 192 SQ. FT. ADDED, 219 SQ. FT REMOVED, shown on the site plan.

3. D.S. 2-02.2.1.A.12 It is not clear where existing and proposed sidewalks start and stop, please clarify. Provide dimensions for the width of all proposed sidewalks. It does not appear that the sidewalk at the northwest corner of the proposed expansion meets the minimum five (5) foot width, see Per D.S. 3-05.2.2.B.1.

4. D.S. 2-02.2.2.A.4 Clarify how the number of required vehicle parking spaces has decreased from the last approved site plan to this plan when basically the same calculation has been provided and building square footage is expanding.

5. D.S. 2-02.2.2.A.6 The building expansion calculation is not correct. Per LUC Sec 3.3.3.12.D building expansions are cumulative. Based on the numbers provided on this plan total square footage add from the "ORIGINAL" = 16,845 SQ. FT. / 65,817 = 25.6% expansion. This includes the 7th ADDITION, see comment 2 above. Based on the numbers provided a site plan showing full code compliance is required.

6. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t08cm00655.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/06/2008 STEVE SHIELDS ZONING HC SITE REVIEW Denied See Zoning comments
03/07/2008 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
03/07/2008 SUE REEVES REJECT SHELF Completed