Permit Number: T08CM00644
Parcel: 11011369B

Address:
4881 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00644
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2008 DAVE MANN FIRE REVIEW Approved
05/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL DESIGN REVIEW COMMENTS:

1. SHEET S3.1; FLOOR FRAMING PLAN: VERIFY THAT JG3 SHOULD BE JG2.
2. SHEET S3.1; STAIR #2: STAIR BEAM SB2 SHOWS UP IN CALCULATIONS AS 12 X 2 X 3/8 (B21) BUT REFERENCE B19 (12 X 2 X 3/16). CLARIFY.
3. SHEET S2.1; CALCULATION SHEET 111: FOOTING F2 AS INDICATED AT GRIDS A-5 AND A-1 DOES NOT MATCH CALCULATIONS F5. CLARIFY.
4. SHEET S2.1; CALCULATION SHEET 112: THE FOUR SHEAR WALLS ARE TYPICALLY ON F6 FOOTINGS, NOT CONTINUOUS WALL FOOTING PER CALCULATIONS. PLAN NOTE INDICATES USE OF F6 FOR SHEAR WALLS, BUT CALCULATIONS DO NOT VERIFY.
5. SHEET S5.1: VERIFY LOCATION OF SECTION 214.
05/09/2008 JASON GREEN ENGINEERING REVIEW Approved Re-stamp
05/13/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. On Panel Schedule IA-22, and 1A-24, please remove the word "EQUIP ROOM' from the description. This is for the elevator cab, per Keynotes 2 and 3 on Sheet E5.1 and NEC 620.22.
2. Provide a disconnecting means for the Elevator Sump Pump.
3. Please specify that elevator pit and machine room receptacles are GFCI protected. Contractors are starting to dispute this item in the field.
4. Elevator equipment room lighting and receptacle not in compliance with NEC 620.23. THIS COMMENT WAS MADE ON THE FIRST SUBMITTAL. Please reinstate receptacle in Elevator Equipment Room, reference NEC 620.23(C). Fixture BE in Elevator Equipment Room should be on receptacle circuit, reference 620.23 (A), not on 1A-3. Add switch in Elevator Equipment Room, reference NEC 620.23 (B).
5. On the Lumen Calculations for Parcel 3, there are a total of 108,000 + 7400 new mean lumens for this 0.94 acre site. So this WOULD require a Special Inspection. However, please note that if there are only 2 new 250W HPS fixtures to be installed in this parcel as seen in the "QTY" column, then the total becomes 54,000 + 7400 = 61,000. Please clarify. See Section 16.
05/13/2008 GERRY KOZIOL WWM REVIEW Denied 1:ASSOCIATES IN WOMEN'S HEALTH CARE
2:NEEDS TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER-NEED TO REVOEW ON-SITE PRIVATE SEWER- ADEQUACY- OVER OR UNDER 3000 GAL/DAY
3:CANNOT DRAIN ELEVATOR PIT TO SEWER (IF CONNECTING TO PUBLIC SEWER WILL NEED WW/IWC REVIEW FOR CONNECTION TO SEWER WITH GREASE INTERCEPTOR- TOM TOMCHAK (579-5771)
05/13/2008 STEVE SHIELDS ZONING REVIEW Approved
05/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The overflow drain for the interior water feature, P12, appears to have a trap arm that exceeds the maximum length for 2" pipe. Include this section of waste and vent piping on riser diagram 1/P2.2. Reference: Sections 103.2.3 and 1002.2, UPC 2006.
2. Comment not addressed by the architect. Clarify the width of the roof scuppers. The roof plan (1/A5.0) shows an 8" width but detail 4/A5.0 shows a 1'-2" width. Reference: Sections 1-3.2.3 and 1101.11, UPC 2006.
3. Comment not addressed by the architect. Show how the roof section at the southeast corner of the building is to be drained. Reference: Sections 1-3.2.3 and 1101.11, UPC 2006.
05/15/2008 ROBERT SHERRY WATER REVIEW Approved
05/15/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Sign and seal the Compliance Statement for the energy conservation code calculations (envelope). Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2008 SUE REEVES OUT TO CUSTOMER Completed
05/22/2008 CPIERCE1 REJECT SHELF Completed