Permit Number: T08CM00644
Parcel: 11011369B

Address:
4881 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM00644
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2008 DAVE MANN FIRE REVIEW Approved
03/12/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A1.0
1. TOILET FIXTURE REQUIRED COUNT AND THAT PROVIDED IS WRONG, RECONFIGURE
SHEET A1.1
1a. ACCESSIBLE CODE TO BE USED IS ICC/ANSI 117.1 2003 EDITION AS REFERENCED TO BY THE IBC 2006 SECTION 1101.2
2. ACCESSIBLE PARKING LAYOUT PRESENT SEVERAL PROBLEMS
A. TRUNCATED DOME DETACTABLE WARNING STRIP CUTS ACCESSIBLE PATH IN HALF AND DOES NOT ALLOW FULL 3' WIDTH FOR WHEEL CHAIR ACCESS (ANSI 403.5) AND DOES NOT MEET REQUIREMENTS OF ANSI 405, 406 AND 705.
B. PARKING SURFACE FLUSH WITH CONCRETE WALK DOES NOT PROVIDE A PHYSICAL BARRIER FOR ACCESSIBLE ROUTE
C. SIGNAGE LOCATION APPEARS REMOTE TO THE PARKING SPACES
D. RECESSED ACCESSIBLE ROUTE CONCRETE WALK PRESENTS A POSSIBLE TRIPPING HAZARD

A SIMPLER SOLUTION IS TO PROVIDE RAISED CURB SEPARATION FROM ACCESSIBLE PARKING SPACES TO CONCRETE WALK AND INSTALL CONCRETE CURB RAMPS (ANSI 406) AT END OF BOTH ACCESSIBLE ISLES WITH A DETACTABLE WARNING STRIP (ANSI 406.12) AT THE BASE OF THE RAMP.


N THIS AREA AS PER ANSI 406.12. PROVIDE AT BASE OF 1:12 RAMP FROM RAISED SIDEWALK.
SHEET A2.1
4. FOR BOTH A AN B RECEPTION COUNTERS, COMPLY WITH ANSI 308.3.2 AND IBC 1109.12.3 WHICH PROVIDES FOR A 2'-10" HIGH BY 3' WIDE SERVICE COUNTER TOP AREA.
SHEET A-5.0
5. SHOW ROOF SLOPE
STRUCTURAL DRAWINGS
6. ALL LETTERING TO BE MINIMUM OF 1/8" HIGH
7. DERFIRRED SUBMITTALS MUST BE APPROVED BY BUILDING OFFICAL AND APPROVAL LETTER MUST BE SUBMITTED WITH DOCUMENTS
8. PROVIDE STRUCTURAL CALCULATIONS FOR ALL ROOF MOUNTED EQUIPMENT
9. PROVIDE STRUCTURAL CALCULATIONS FOR ALL STRUCTURAL DESIGN. A COMPLETE STRUCTURAL REVIEW CAN NOT BE COMPLETED WITHOUT CALCULATIONS.
10. PROVIDE STRUCTURAL CALCULATIONS FOR LIGHT POLE FOUNDATIONS
GENERAL
11. Provide a separate architectural site plan showing all site amenities:
a. Drive and walkways
1. All accessible routes from public transportation to the accessible front entrances are to be identified
2. All accessible routes from accessible parking spaces to accessible front entrances are to be identified
3. Slopes for all accessible routes are to be noted and further clarified by providing spot elevations at appropriate locations to evaluate slope design
b. Parking layout
1. Show accessible spaces plus spot elevations for slope compliance
c. Paved areas and types of paving
d. Building footprint and configuration with entrances and exists identified
e. Landscape areas
f. Property lines
g. Streets, easements and R.O.W.s
h. Fences, curbs, ponding areas, drainage structures and etc
i. Dimension all elements of construction shown on the site plan
03/18/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed No impact fee's, building permit is exempt per exemption 1 under Section 23A-86 on a new building. DP approved on 9/28/06 and will expire 9/28/08.
03/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008)
2. Provide a cleanout for the horizontal drain (UG) for P-11 (room 239). Reference: Section 707.4, UPC 2006.
3. Clarify the model of water cooler specified (Elkay EFRC-8) and how it relates to the depiction of the unit on the floor plans and riser diagrams. Reference: Section 103.2.3, UPC 2006 and Section 1109.5, IBC 2006.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Keynotes 53, 54, and 55 on sheet P1.1 identify an overflow drain from an interior water feature. Only rainwater may be discharged at the curb face; connect the overflow to the sanitary drain system. Reference: Section 304.0, UPC 2006.
6. The elevator sump pump may not discharge to grade but must discharge to the sanitary sewer by way of a sand/oil separator. Reference: Sections 304.0, 805.0, and 1009.0, UPC 2006.
7. Clarify how P-5 is associated with the autoclave and how the autoclave will be drained. Reference: Sections 103.2.3 and 801.5, UPC 2006.
8. Clarify the width of the roof scuppers. The roof plan (1/A5.0) shows an 8" width but detail 4/A5.0 shows a 1'-2" width. Reference: Sections 1-3.2.3 and 1101.11, UPC 2006.
9. Show the roof section at the southeast corner of the building is to be drained. Reference: Sections 1-3.2.3 and 1101.11, UPC 2006.
03/20/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations. Reference: Section 101.4, International Energy Conservation Code 2006.
2. Correct the "occupancy category" for the restrooms to show that they are all public restrooms. "Private" for plumbing fixtures (e.g. "Toilets - Private", sheet M2.2) applies to fixtures that are intended for the use of a family or an individual. Reference: Section 218.0, UPC 2006.
3. Provide listing information for the clothes dryer to show that the proposed dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6, IMC 2006.
4. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006
03/20/2008 ROBERT SHERRY WATER REVIEW Approved
04/02/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Circuit IA-28,30, as shown on E3.1, only powers electrical loads on Ckt 28. Please clarify.
2. There are two receptacles, one in the pit, and one in the elevator equipment room, on Ckts 28 and 30 respectively, no panel. Please clarify.
3. Ckt IA-28, as shown on the panel schedule, appears to violate the separate branch circuit requirement for the pit in NEC 620.24 (A) because of the receptacle in the equipment room on Ckt 28.
4. Elevator is 20HP per E3.1, and 25 HP on line diagram E5.1.
5. Elevator equipment room lighting and receptacle not in compliance with NEC 620.23.
6. Please correct the designation "2B-5,7" on Sheet E2.2 to read "2B-3,5,7."
7. Please allocate electrical load for Water Feature. Ckt 1A-40,42.
8. Please correct the designation "2A-19,21,25" on Sheet E3.2 to read "2A-19,21,23."
9. Provide GFCI protected outlets for the vending machines per NEC 422.51, as appropriate.
10. It appears that fax and copy machines on Ckts 2B-11 and 2A-8,10 would have more electrical load than is indicated on the panel schedules.
11. There are two panels "AC". It appears that the one which powers the fan coils should be labeled "ACA."
12. Provide conductor size for home run on Ckt ACA-2,4.
13. Provide conductor size for home run on Ckt ACA-8,10,12.
14. Please specify the Main Bonding Jumper size on the Single Line Diagram as 200 MCM. Reference NEC 250.28 (D).
15. Please provide a maintenance receptacle within 25' of HP-3. Reference NEC 210.63.
16. Fill in the electrical load on the panel schedule for HP-7.
17. The 90A CB on Ckt AC-2,4,6 is too large for Ground Fault and Short Circuit Protection, and for the size of the conductor.
18. On the HVAC Power Plan, please correct "1Ø" to read "3Ø."
19. The 70A CB on Ckt AC-14,16,18 is too large for Ground Fault and Short Circuit Protection. Please correct here and all others which may apply.
20. Provide fault current rating of service disconnect switch.
21. It appears that Fault #4 is aprox. 13,603A, not 103,518A.
22. It appears that Panel 2A is 45' from the service, not 110'. So the AFC is very close to 22K. Please revisit this.
23. Provide fault calculations for Panels AC and ACA.
24. Demonstrate compliance with the 2006 IECC.
25. Demonstrate compliance with Tucson Lighting Code.
26. Please make it absolutely clear that all work in patient care areas shall comply with NEC 517.13. Suggest an additional note on the power plans.
04/03/2008 STEVE SHIELDS ZONING REVIEW Approved
04/03/2008 JASON GREEN ENGINEERING REVIEW Approved
04/14/2008 GERRY KOZIOL WWM REVIEW Denied 1:ASSOCIATES IN WOMEN'S HEALTH CARE
2:NEEDS TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER-NEED TO REVOEW ON-SITE PRIVATE SEWER- ADEQUACY- OVER OR UNDER 3000 GAL/DAY