Permit Number: T08CM00604
Parcel: 13734001E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00604
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/29/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; West District; 1,200 Square Feet; $4,771.20
05/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The design of the water heater piping, with a shutoff valve located between the water heater and both the expansion tank and the vacuum relief valve, makes it impossible for them to operate properly. Reference: Sections 608.3 and 608.7, UPC 2006
2. Based on the shell building water calculations, which show 5.8 PSI available for friction, several of the water pipes are too small. Reference: Sections 610.4 and 610.5, UPC 2006. (Note that the substitution of PEX tubing for the copper will require a separate calculation for determining the required sizes for PEX, based on the specified manufacturer's recommendations and a maximum water velocity of 8 FPS.)
3. Comment not resolved, see P-7, located along the east wall of the suite. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006
4. The floor drain, P-6, is shown on the fixture schedule and the water calculations but is not shown on the plumbing plan. It is required per Section 704.3, UPC 2006.
5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
05/01/2008 ROBERT SHERRY WATER REVIEW Approved
05/02/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/22/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2008 VFLORES1 OUT TO CUSTOMER Completed