Review Details: RESUBMITTAL - SITE
Permit Number - T08CM00601
Review Name: RESUBMITTAL - SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Wildcat Automotive - Addition T08CM00601 Site Plan (3rd Review) TRANSMITTAL DATE: November 13, 2008 COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance. 2. This comment was not addressed. D.S. 2-02.2.2.3 The "ACTUAL F.A.R." should include the existing building and the expansion, please revise. 3. Once the above comment has been addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this over-the-counter review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\site\t08cm00601-2nd RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents. |
| 11/19/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the location and size of the public sanitary sewer b. the location, invert, and rim elevation of all manholes c. the first floor elevation of the building Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006. |