Permit Number: T08CM00601
Parcel: 115060010

Address:
2050 N ORACLE RD

Review Status: Completed

Review Details: SITE

Permit Number - T08CM00601
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2008 DAVE MANN FIRE REVIEW Approved
06/19/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 1. SHOW SLOPES OF ALL ACCESSIBLE ROUTES BEING IN COMPLIANCE WITH 2006 IBC/ICC 117.2, SECTION 403.3.
2. NOTES 3 AND 4 SHEET D-2: CHANGE 36" TO 48"
3. ADD 2' DEEP DETECTABLE WARNINGS AT THE BOTTOM OF ALL MARKED CROSSING RAMPS AND AT THE EDGE FROM THE ACCESSSIBLE ROUTE TO THE PAAL AT THE OPPOSITE END OF THE MARKED CROSSING AS PER 2006 IBC/ICC 117.2, SECTIONS 406.12 AND .13.
4. CHANGE DIMENSION 4' WIDTH FOR BOTH RAMPS TO 5'-0".
5. PROVIDE DETAIL AND SHOW LOCATION OF ACCESSIBLE PARKING "VAN ACCESSIBLE" SIGN.
6. MAINTAIN 4' WIDE MINIMUM CONCRETE WALK WIDTH AT ACCESSIBLE ROUTE CONNECTION TO R.O.W. CONCRETE WALK WAY.
06/24/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Wildcat Automotive - Addition
T08CM00601
Site Plan (1st Review)

TRANSMITTAL DATE: June 25, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. Provide a copy of the last approved site plan with your next submittal. This site plan should show the addition of the existing service bay located at the south end of the existing building and the existing awning attached to the west side of the existing building. If the last approved site plan does not show either of these additions, permits will be required.

3. Add a note to the plan stating that the project is designed to meet the overlay zone(s) criteria: Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone; Sec. 2.8.4, Gateway Corridor Zone;

4. D.S. 2-02.2.1.A.5 Provide lot dimensions and bearings for all lot lines on the plan.

5. D.S. 2-02.2.1.A.6 Provide overall dimensions for the proposed addition on the plan.

6. D.S. 2-02.2.1.A.8 Provide typical parking space details for both handicapped and standard spaces. Include a dimension for wheel stop locations and the 1:48 maximum slopes for the handicapped vehicle parking space and the access aisle on the handicapped parking space detail. The parking shown along the west side of the existing building appears to hang over the sidewalk but appears to still allow for the four (4) wide sidewalk, ensure this is demonstrated on the detail and or plan.

7. D.S. 2-02.2.1.A.8 Provide a dimension for the proposed parallel parking spaces. The western most parallel parking space is not allowed to encroach into the future sight visibility triangle (SVT), revise the plan.

8. D.S. 2-02.2.1.A.8 Per LUC Section 3.3.3.9 Areas That May Not Be Used For Required Parking. Parking spaces shall not be located under, or within five (5) feet of, a vertical line intersecting the ground and any structural element extending from a billboard, including, but not limited to, overhangs, cantilevered beams, and elevated walkways. This said the two parallel parking spaces may not be located as shown.

9. D.S. 2-02.2.1.A.8 As the vehicle parking shown directly to the north and behind the existing building is required parking the parking area access lane (PAAL) must meet the minimum width for a two-way PAAL of twenty-four (24) feet.

10. D.S. 2-02.2.1.A.8 The proposed gate for the load space area appears to encroach into the two (2) foot six (6) inch vehicle overhang of parking space number 12.

11. D.S. 2-02.2.1.A.11 If the fence, called out under keynote 13 is to remain then the eastern most entrance PAAL off of Flores Street will need to be closed off to prevent parking and/or vehicles trying to maneuver in and out of this area.

12. D.S. 2-02.2.1.A.12 A backup spur is required to at the north end of the parking located northeast of the existing building. See D.S. 3-05.2.2.D Back-Up Spur. A back-up spur will be provided at the end of a row of parking if no ingress or egress is provided at that end. The spur will be a minimum of three (3) feet in depth, will have a three (3) foot radii, and will have a wheel barrier to prevent encroachment onto any un-surfaced areas. A minimum distance of three (3) feet will be provided between the back of spur and any wall, screen, or other obstruction over six (6) inches in height.

13. D.S. 2-02.2.1.A.12 It appears that the electrical service encroaches into the required ten (10) foot wide parking space, number 14, at the rear of the building.

14. D.S. 2-02.2.1.A.12 Provide a detail for the proposed handicapped ramps adjacent to the building. It does not appear that the minimum four (4) foot width is maintained between the curbing.

15. D.S. 2-02.2.1.A.12 It is not clear how the accessible route that runs north gains access to the existing sidewalk at the access island. Is the sidewalk flush with pavement or is there a ramp?

16. D.S. 2-02.2.1.A.12 The sidewalk shown along the north side of the building is required to be four (4) foot wide. Also a man gate is required at the sidewalk area.

17. D.S. 2-02.2.1.A.12 Per D.S. 3-05.2.1.4.a The minimum height clearance for access along PAALs is fifteen (15) feet. This said the existing canopy, 13'-6" Clear Ht, across the entrance PAAL off of Oracle Road does not meet this requirement.

18. D.S. 2-02.2.1.A.12 The striped area adjacent to the handicapped vehicle access aisle is required to be a sidewalk the entire length of the access aisle, physically separated from the PAAL accessing the service bays.

19. D.S. 2-02.2.1.A.18 Label Oracle Road as a MS&R and Gateway Corridor.

20. D.S. 2-02.2.1.A.20 If applicable show all easements of record graphically on the plan together with recording docket and page reference.

21. D.S. 2-02.2.2.3 The "ACTUAL F.A.R." should include the existing building and the expansion, please revise.
.
22. D.S. 2-02.2.2.4 The MS&R reduction is not correct. The 6.7% should be used as a factor of .067 x 1000 = 67, the 67 is than added to the 1000 for a ratio of 1 space per 1067 gross lot area. The final parking calculation should end up as 16,500 / 1067 = 15.4 or 15 vehicle parking spaces require. Please revise the parking calculation.

23. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t08cm00601

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
07/01/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Within vehicular use areas, one (1) canopy tree is required for each 10 motor vehicle parking spaces or fraction thereof, and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Revise plan drawing and canopy tree calculation on landscape plan accordingly. Also, the drawing shows 16 vehicle parking spaces but the calculation on the landscape plan states that there only 14 spaces provided. Revise as necessary.

2. Landscaping along parking lots where plants are susceptible to injury by vehicular traffic must be protected by appropriate means, such as curbs, bollards, or low walls per LUC 3.7.2.3.B. Revise planter on the east side of the parking lot to show curbing or other means of protection as necessary.

3. Dimension the minimum width and label the square footage measured from the inside of tree planters in the vehicle use area. An unpaved area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree.
LUC 3.7.2.3.A.1.c, DS 2-07.2.2.A.2.e

4. Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee, up to five (5) feet of the required ten (10) foot width be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Dimension the width of landscape border within the MS&R right-of-way as well as the portion to be provided on the site. Landscape borders proposed in right-of-way areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect for specific requirements.
LUC 3.7.2.4.A.3

5. Provide a copy of the last approved landscape plan and site plan. Additional comments may apply upon resubmittal.
07/02/2008 PETER MCLAUGHLIN NPPO REVIEW Approved Exception.
07/14/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Jim Watson, AIA DATE: July 14, 2008
Architecrt 3026 N. Country Club Road Tucson, Arizona 85716

SUBJECT: Wildcat Automotive, 2050 N. Oracle Road
Site plan T08CM00601 (First Review)
T14S, R13E, Section 01

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
3. Please label lot dimensions and bearings per D.S. 2-02.2.1.5
4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
5. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
6. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
7. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
8. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP.
9. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
10. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
11. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
12. Show Site plan number (T08CM00601) on all sheets per D.S. 2-02.2.1.29.
13. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Obtain permission from Environmental Services for the use of roll-out containers.
14. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
15. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
16. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations and/or other sidewalk scuppers have been designed and located will suffice.
17. List the consulting engineer and the owner/developer on the plans with the pertinent information.
18. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DS.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:\2050 N. Oracle Road_Site

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2008 VFLORES1 OUT TO CUSTOMER Completed