Permit Number: T08CM00594
Parcel: 14111027B

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T08CM00594
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2008 TERRY STEVENS ZONING REVIEW Needs Review
03/21/2008 TERRY STEVENS ZONING_QA REVIEW Passed
03/21/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
03/21/2008 BIANCA RAMIREZ ENGINEERING_QA REVIEW Passed
03/21/2008 CPIERCE1 FIRE REVIEW Needs Review
03/21/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: August 26, 2009
SUBJECT: 7475 S Old Vail Road Building Plan- Engineering Review
TO: Mike Kreus
LOCATION: T15S R15E Sec21 Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: T08CM00594 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T08CM00594) for the above referenced property. Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved development plan (D08-0021). Please submit two copies of the stamped approved development plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved development plan. Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2008 CPIERCE1 OUT TO CUSTOMER Completed