Permit Number: T08CM00580
Parcel: 112060040

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00580
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
02/20/2008 JASON GREEN ENGINEERING REVIEW Approved
02/21/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00580 2/21/08

1. Provide panel and circuit number for all new electrical loads. Several new receptacles are shown without this.
2. Provide panel schedule and load calculations.
3. For the ultrasound, please specify that the wiring shall comply with NEC 517.13.
02/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/21/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. FIX SALOON DOORS TO HAVE A MIN OF 2'-10" CLEAR FOR ACCESSIBILITY
2. REVERSE SWING OF MAIN CONFERENCE ROOM DOOR
3. AS PER IBC 3409.7 ACCESSIBILITY EXPENDITURES ARE NOT REQUIRED TO EXCEED 20%. PROVIDE COST BREAK DOWN SHOWING EXPENDITURES
4. PROVIDE BUILDING CODE ANALYSIS DATA FORM
02/21/2008 ROBERT SHERRY WATER REVIEW Approved
02/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/21/2008 MARTIN BROWN FIRE REVIEW Approved
02/25/2008 GERRY KOZIOL WWM REVIEW Approved
02/25/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2008 DELMA ROBEY OUT TO CUSTOMER Completed