Permit Number: T08CM00552
Parcel: 11106395A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO

Permit Number - T08CM00552
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2008 LOREN MAKUS ENGINEERING REVIEW Approved
03/27/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water isometrics and waste and vent isometrics. Reference: Section R106.1.1, IRC 2006.
2. Provide the sizing calculations for the water distribution piping. If the materials used for the water distribution are not as specified on the drawing, provide additional sizing calculations for the alternate material. Reference: Sections R106.1.1 and P2903.7, IRC 2006.
3. Based on the submitted calculations, the demand for this activity is 15 GPM. Tucson Water limits a 5/8" meter (there are no ¾" meters) to demands of 10 GPM or less and 1" meters to demands of 25 GPM or less.
4. Provide the dimensions of the scuppers for the roof drainage.
5. Provide equipment data for the water heater. Reference: Section R106.1.1, IRC 2006.
6. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves.
03/27/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. FLOOR PLAN (SHEET 1) AND FOUNDATION PLAN (SHEET 2): INDICATE ALL HOLDOWNS PER BRACE PANEL SCHEDULE ON SHEET 1.
2. COMPLETE BEAM POST FOOTING CONN. SECTION ON SHEET 2.
03/27/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the building complies with the requirements of Section 401.2, IECC 2006.
2. Show how makeup air will be provided to the dryers.
3. Clarify the type of rooftop unit being installed. The units are called out as both heat pumps and gas-fired A/C units.
03/27/2008 GERRY KOZIOL WWM REVIEW Denied 1:needs to show location & method of connection to public sewer
2:needs 8th floor wastewater review of location & method of connection to public sewer.
3:needs wastewater review of easements joint use agreement
03/28/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2008 DELMA ROBEY OUT TO CUSTOMER Completed
04/08/2008 SHANAE POWELL REJECT SHELF Completed