Permit Number: T08CM00549
Parcel: 12216224A

Review Status: Completed

Review Details: MODULAR BUILDINGS

Permit Number - T08CM00549
Review Name: MODULAR BUILDINGS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Impact Fee's Do Apply; Central District; 4,576 Square Foot Modular Building; $
08/11/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Emmanuel Baptist Church - Modular Office Building
T08CM00549
Building Plan (1st Review)

TRANSMITTAL DATE: August 11, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm00549.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
08/11/2008 DAVE MANN FIRE REVIEW Approved
08/12/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Passed All modular buildings are regulated and permitted by the state
08/20/2008 GERRY KOZIOL WWM REVIEW Denied NEEDS FLOOR PLAN & PLUMBING PLANS
08/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/21/2008 ROBERT SHERRY WATER REVIEW Denied 1. Show a reduced pressure backflow prevention assembly for the water service to the new modular building. Reference Section 27-75 (27), COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Show the size of the water meter for the proposed modular office building. The maximum demand flow that is allowed by Tucson Water for a 5/8" water meter is 10 GPM, 25 GPM for a 1" meter, 50 GPM for a 1-1/2" meter, and 80 GPM for a 2" meter. In addition, Tucson Water does not supply any ¾" water meters.
09/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide electrical plans for the site electrical intended to power the new modular building, up to the service disconnecting means.
09/10/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: September 10, 2008
SUBJECT: Site Compliance Permit
TO: Jerry Cox
LOCATION: 1825 N Alvernon, T14S, R14E, Section 4, Ward 6
REVIEWERS: Loren Makus, EIT
ACTIVITY: T08CM00549 (Second Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following
review comments prior to the next submittal.

Include a response letter to the comments along with the corrected copies of the site plan.

Site Plan:
Show the future sight visibility triangles along with the existing sight visibility triangles. The future triangles should be aligned with the future curb location which is nine feet from the edge of the future right-of-way.

List the estimate cut and fill quantities for this project as indicated in the previous review.

Show the drainage patterns for the roof of the modular building. Show that roof drainage will not be directed over adjacent sidewalks.

Loren Makus
Senior Engineering Associate
Loren.makus@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2008 DELMA ROBEY OUT TO CUSTOMER Completed
09/17/2008 SUE REEVES REJECT SHELF Completed