Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM00537
Parcel: 13734001D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00537
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2008 DAVE MANN FIRE REVIEW Approved
02/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/19/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00537 2/18/08

1. Reference to grounding of communications systems is NEC 800.100, not 400.80.
2. Overcurrent protection for WH properly sized at 25A, not 30A. Reference NEC 422.10.
3. Please complete the calculation for IECC compliance. We see how many watts are installed, but not how many are allowed for this space. Note that Area Category Method counts Retail at 6031 SF, whereas Entire Building Method counts the whole space at 1586 SF, a smaller number.
4. With 18.1 KA available, please upgrade the rating of this 10,000 AIC panel. Also please correct the "18.1 A" designation to read "18.1 KA."
02/19/2008 ROBERT SHERRY WATER REVIEW Approved
02/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/20/2008 GBONILL1 WWM REVIEW Needs Review
02/20/2008 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
02/20/2008 GBONILL1 ENGINEERING REVIEW Needs Review
02/20/2008 GBONILL1 ZONING REVIEW Needs Review
02/20/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review