Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00537
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/19/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 02/19/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/19/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00537 2/18/08 1. Reference to grounding of communications systems is NEC 800.100, not 400.80. 2. Overcurrent protection for WH properly sized at 25A, not 30A. Reference NEC 422.10. 3. Please complete the calculation for IECC compliance. We see how many watts are installed, but not how many are allowed for this space. Note that Area Category Method counts Retail at 6031 SF, whereas Entire Building Method counts the whole space at 1586 SF, a smaller number. 4. With 18.1 KA available, please upgrade the rating of this 10,000 AIC panel. Also please correct the "18.1 A" designation to read "18.1 KA." |
| 02/19/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/19/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/20/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 02/20/2008 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/20/2008 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
| 02/20/2008 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 02/20/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |