Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Permit Number - T08CM00535
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2008 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T08CM00535 3/20/08 4013 E. 26th STREET PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. LABEL ALL ROOMS AND SPACES. PLEASE IDENTIFY THE 3' ROOM BETWEEN THE STORAGE ROOM AND THE EXISTING BEDROOM. DOES IT NEED A DOOR, A WINDOW, etc.? 2. DESIGNATE THE OPERABLE PORTION OF WINDOWS. 3. THE 4X8 BEAM ON THE PORCH APPEARS TO BE LABELED AS A 4X4 POST. PLEASE CORRECT. 4. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT. STRUCTURAL PLANS: 1. SPECIFY LUMBER GRADE AND SPECIES. 2. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. 3. SPECIFY LATERAL SUPPORT OF TRUSSES. 4. DETAIL GABLE END BRACING CONNECTIONS. SECTIONS - DETAILS - MISC. NOTES: 1. ON STANDARD DETAIL SHEETS, CROSS-OUT ALL DETAILS AND NOTES THAT DO NOT APPLY OR WERE NOT USED. 2. KEYNOTE E / 2 ; 2X4s WON'T ACCOMMODATE 5-1/2" INSULATION. 3. KEYNOTE E / 2 ; IS THE T-111 A TYPO? 4. 4. KEYNOTE P IS MENTIONED ON THE RIGHT SIDE OF THE ADDITION ON DRAWING NO. 2. WHERE IS IT? TYPO? 5. 2 / 4 ; THE FRIEZE BOARD IS LABELED AS A SKYLITE. PLEASE CORRECT. 6. 2 / 4 ; JUSTIFY THE R-13 INSULATION IN THE ROOF. SEE TABLE E 1102.1. OR "RES-CHECK". PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. 2. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES. SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED CLEANOUTS. 3. IS THERE A WATER HEATER IN THE LAUNDRY? IF SO, PROVIDE GAS OR ELECTRICITY TO IT. 4. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH ELECTRICAL PLANS: 1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. 2. PLAN SHOWS THE DRYER ON CIRCUIT ON #3,5 BUT THE SCHEDULE SHOWS IT ON #8,10. PLEASE CORRECT. 3. CIRCUIT #2 IS FOR THE KITCHEN ACCORDING TO THE PANEL SCHEDULE. PLEASE CORRECT. 4. CIRCUIT #4 IS TO SERVE A BATH ROOM PER THE PANEL SCHEDULE. PLEASE CORRECT. 5. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT THE BACK OF THE DWELLING, PER E3801.7. 6. PROVIDE A LIGHT OUTSIDE THE LAUNDRY ROOM DOOR. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/27/2008 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 03/27/2008 | SHANAE POWELL | REJECT SHELF | Completed |