Permit Number: T08CM00522
Parcel: 13104405A

Address:
4925 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00522
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2008 DAVE MANN FIRE REVIEW Approved
04/03/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/03/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/03/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Size the drain piping per Table 7-5, UPC 2006. The minimum drain pipe size for a water closet is 3".
2. A 1/2" water line to a urinal flush valve will result in water velocities greater than 8 fps. Provide calculations to show that the pipe sizes are justified.
3. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the temperature limit stop on the lavatory faucet is to be adjusted to guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
04/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/09/2008 CAGUILA1 WWM REVIEW Needs Review