Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00522
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/15/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
04/03/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/03/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/03/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Size the drain piping per Table 7-5, UPC 2006. The minimum drain pipe size for a water closet is 3". 2. A 1/2" water line to a urinal flush valve will result in water velocities greater than 8 fps. Provide calculations to show that the pipe sizes are justified. 3. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the temperature limit stop on the lavatory faucet is to be adjusted to guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
04/03/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/03/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/09/2008 | CAGUILA1 | WWM | REVIEW | Needs Review |