Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM00522
Parcel: 13104405A

Address:
4925 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00522
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2008 STEVE SHIELDS ZONING REVIEW Approved
02/15/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference Section 503.2.7, IECC 2006, as amended by the City of Tucson.
3. Provide manufacturer's equipment data along with mechanical and electrical operating information for the new evaporative cooler (i.e. finish filling in the schedule). Reference Section 301.6, IMC 2006.
4. Revise the size of the condensate drains per Section 307.2.2, IMC 2006, as amended by the City of Tucson.
5. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2006.
6. Provide calculations to show that the common ventilation system for HP-2 is sized in accordance with Section 403.3.2, IMC 2006.
02/15/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00522 2/15/08

1. Provide overload protection, ground fault and short circuit protection for the EC.
2. Provide power for the Little Giant Sump Pump referenced on Sheet P-1 Keynote 1.
02/15/2008 ROBERT SHERRY WATER REVIEW Approved
02/15/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL CALCULATIONS FOR NEW EVAPORATIVE COOLER ON EXISTING ROOF.
2. VERIFY NEW ROOFTOP HEAT PUMPS ARE COMPARABLE IN WEIGHT TO EXISTING PUMPS.
02/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Complete the waste and vent isometrics. Reference Section 103.2.3, UPC 2006.
2. Provide fixture descriptions or material standards for all new plumbing fixtures. Reference Section 401.1, UPC 2006.
3. Show that the floor of the restroom slopes toward the floor drain. Reference Section 411.2, UPC 2006.
4. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference Section 402.1, UPC 2006, as amended by the City of Tucson.
5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
6. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 2006.
03/18/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/03/2008 GBONILL1 FIRE REVIEW Needs Review
04/03/2008 GBONILL1 WWM REVIEW Needs Review
04/03/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Denied