Permit Number: T08CM00520
Parcel: 137055110

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00520
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2008 DAVE MANN FIRE REVIEW Denied Mechanical sheets refer to a Type II hood that contains grease filters. Grease laden vapors require Type I hood with wet chemical fire suppression system.
04/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Detail 7/P3.0 calls out an indirect waste receptor for the cooler/freezer. Where is it located? Reference: Section 103.2.3, UPC 2006.
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. The design of the water heater piping, with a valve located between the water heater and the expansion tank, makes it impossible for the expansion tank to accommodate the thermal expansion of the water in the water heater, as intended by Section 608.3, UPC 2006.
4. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0 and 801.2.3, UPC 2006.
5. Provide a floor drain adjacent to the 3-compartment sink per Section 704.3, UPC 2006.
04/30/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The approval letter from the City of Los Angeles allows the use of a type II hood for the Holman QT14 conveyor oven provided that neither the menu items prepared in the oven nor the operating conditions of the oven are modified. The City of Tucson bases the hood requirement on the type of equipment that is to be located below the hood, not the proposed menu items. Provide a Type I hood over conveyor oven. Reference: Sections 507.1 and 507.2, IMC 2006.
2. Show that the clearances for the grease duct comply with Section 506.3.6, IMC 2006.
3. Revise the size of the grease ducts to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
4. Provide a grease drain and collection reservoir for the vertical discharge fan. Reference: Section 506.5.2, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
06/16/2008 SHANAE POWELL REJECT SHELF Completed