Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00520
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/15/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/19/2008 | DAVE MANN | FIRE | REVIEW | Denied | Mechanical sheets refer to a Type II hood that contains grease filters. Grease laden vapors require Type I hood with wet chemical fire suppression system. |
02/20/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/22/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE BUILDING CODE DATA FORM. REEFERENCE CITY OF TUCSON WEB SITE; BUILDING AND SIGN PERMITS 2. OBTAIN APPEAL FROM BUILDING OFFICIAL TO USE 3/32" (ALL CAPS) MINIMUM FONT SIZE ON ALL DOCUMENTS. CHANGE ALL FONTS LESS THAN 3/32" TO 3/32" 3. CHANGE ACCESSIBLE CODE STANDARDS REFERENCE FROM ADAAG TO ANSI 117.1 4. REFERENCE ANSI 203.3.11 AND .10 FOR INTERIOR SIGNAGE REQUIREMENTS AND HEIGHT STANDARDS REFERENCE 5. REFRENCE CITY OF TUCSON STANDARDS FOR ACCESSIBLE PARKING SIGNAGE STANDARDS 6. REFENCE ANSI 604.5.1 FOR VERTICAL GRAB BAR REQUIREMENTS 7. REFERENCE ANSI 306.2 FOR CLEAR SPACE REQUIREMENTS AT LAVATORIES 8. REFERENCE ANSI 307.2 FOR MINIMUM PROJECTIONS FROM WALL 9. PROVIDE STRUCTURAL CALCULATIONS FOR WATER HEATER MOUNTING 10. REFERENCE ANSI 406.12, 13, 14, AND 705.5 FOR DETECTABLE AND TRUNCATED DOME WARNINGS AT RAISED MARKED CROSSINGS 11. REFERENCE ARIZONA DEPARTMENT OF TRANSPORATION FOR HEIGHT OF ACCESSIBLE PARKING SIGN MOUNTING; 7'-0" 12. PROVIDE STRUCTURAL CACUILATIONS FOR EXHAUST FAN AND HOOD MOUNTING 13. PROVIDE ORIGINAL SHOPPING SITE PLAN, SHELL DRAWINGS AND SHOPPING CENTER BUILDING CODE DATA |
02/28/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/12/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/14/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | . |
03/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Obtain an appeal from the building official if the design is to be based on the International Plumbing Code. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case) or obtain an appeal from building official to use 3/32" (all caps) minimum font size on all documents; change all fonts less than 3/32" to 3/32". Reference: Section 106.1.1, IBC 2006. 3. Provide water isometrics and waste and vent isometrics. |
03/14/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the status of HP2; it is noted as existing on the packaged heat pump schedule (M1.0) but is not shown on the approved building shell drawings. When was it installed? Reference: Section 106.1.1, IBC 2006. 2. Correct note #11, P2.0 regarding the size of the condensate drain being connected to the lavatory tailpiece. Reference Section 307.2.2, IMC 2006, as amended by the City of Tucson. 3. Provide calculations demonstrating adequate ventilation. Reference: Section 403.0, IMC 2006. 4. Provide a Type I hood over conveyor oven. Reference: Sections 507.1 and 507.2, IMC 2006. 5. Show that the clearances for the grease duct comply with Section 506.3.6, IMC 2006. 6. Revise the size of the grease ducts to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson. 7. Provide a grease drain and collection reservoir for the vertical discharge fan. Reference: Section 506.5.2, IMC 2006. 8. Provide adequate make up air for the kitchen exhaust hood. Reference: Section 508.1 IMC 2006. 9. Clarify the proposed location for the in-duct smoke detectors. Detail 1/M3.0 and the HVAC floor plan (M2.0) locate the detectors in the return ducts (as required by Section 606.2.1, IMC 2006 for air distribution units moving greater than 2,000 CFM) but note #5 of the packaged heat pump schedule (M1.0) calls for the detectors to be mounted in the supply ducts. 10. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case) or obtain an appeal from building official to use 3/32" (all caps) minimum font size on all documents; change all fonts less than 3/32" to 3/32". Reference: Section 106.1.1, IBC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/21/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
03/21/2008 | SUE REEVES | REJECT SHELF | Completed |