Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00520
Parcel: 137055110

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00520
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/19/2008 DAVE MANN FIRE REVIEW Denied Mechanical sheets refer to a Type II hood that contains grease filters. Grease laden vapors require Type I hood with wet chemical fire suppression system.
02/20/2008 GERRY KOZIOL WWM REVIEW Approved
02/22/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE BUILDING CODE DATA FORM. REEFERENCE CITY OF TUCSON WEB SITE; BUILDING AND SIGN PERMITS
2. OBTAIN APPEAL FROM BUILDING OFFICIAL TO USE 3/32" (ALL CAPS) MINIMUM FONT SIZE ON ALL DOCUMENTS. CHANGE ALL FONTS LESS THAN 3/32" TO 3/32"
3. CHANGE ACCESSIBLE CODE STANDARDS REFERENCE FROM ADAAG TO ANSI 117.1
4. REFERENCE ANSI 203.3.11 AND .10 FOR INTERIOR SIGNAGE REQUIREMENTS AND HEIGHT STANDARDS
REFERENCE
5. REFRENCE CITY OF TUCSON STANDARDS FOR ACCESSIBLE PARKING SIGNAGE STANDARDS
6. REFENCE ANSI 604.5.1 FOR VERTICAL GRAB BAR REQUIREMENTS
7. REFERENCE ANSI 306.2 FOR CLEAR SPACE REQUIREMENTS AT LAVATORIES
8. REFERENCE ANSI 307.2 FOR MINIMUM PROJECTIONS FROM WALL
9. PROVIDE STRUCTURAL CALCULATIONS FOR WATER HEATER MOUNTING
10. REFERENCE ANSI 406.12, 13, 14, AND 705.5 FOR DETECTABLE AND TRUNCATED DOME WARNINGS AT RAISED MARKED CROSSINGS
11. REFERENCE ARIZONA DEPARTMENT OF TRANSPORATION FOR HEIGHT OF ACCESSIBLE PARKING SIGN MOUNTING; 7'-0"
12. PROVIDE STRUCTURAL CACUILATIONS FOR EXHAUST FAN AND HOOD MOUNTING
13. PROVIDE ORIGINAL SHOPPING SITE PLAN, SHELL DRAWINGS AND SHOPPING CENTER BUILDING CODE DATA
02/28/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/12/2008 TERRY STEVENS ZONING REVIEW Approved
03/14/2008 ROBERT SHERRY WATER REVIEW Approved .
03/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Obtain an appeal from the building official if the design is to be based on the International Plumbing Code.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case) or obtain an appeal from building official to use 3/32" (all caps) minimum font size on all documents; change all fonts less than 3/32" to 3/32". Reference: Section 106.1.1, IBC 2006.
3. Provide water isometrics and waste and vent isometrics.
03/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the status of HP2; it is noted as existing on the packaged heat pump schedule (M1.0) but is not shown on the approved building shell drawings. When was it installed? Reference: Section 106.1.1, IBC 2006.
2. Correct note #11, P2.0 regarding the size of the condensate drain being connected to the lavatory tailpiece. Reference Section 307.2.2, IMC 2006, as amended by the City of Tucson.
3. Provide calculations demonstrating adequate ventilation. Reference: Section 403.0, IMC 2006.
4. Provide a Type I hood over conveyor oven. Reference: Sections 507.1 and 507.2, IMC 2006.
5. Show that the clearances for the grease duct comply with Section 506.3.6, IMC 2006.
6. Revise the size of the grease ducts to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
7. Provide a grease drain and collection reservoir for the vertical discharge fan. Reference: Section 506.5.2, IMC 2006.
8. Provide adequate make up air for the kitchen exhaust hood. Reference: Section 508.1 IMC 2006.
9. Clarify the proposed location for the in-duct smoke detectors. Detail 1/M3.0 and the HVAC floor plan (M2.0) locate the detectors in the return ducts (as required by Section 606.2.1, IMC 2006 for air distribution units moving greater than 2,000 CFM) but note #5 of the packaged heat pump schedule (M1.0) calls for the detectors to be mounted in the supply ducts.
10. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case) or obtain an appeal from building official to use 3/32" (all caps) minimum font size on all documents; change all fonts less than 3/32" to 3/32". Reference: Section 106.1.1, IBC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2008 VFLORES1 OUT TO CUSTOMER Completed
03/21/2008 SUE REEVES REJECT SHELF Completed