Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM00518
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/23/2008 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS T08CM00518 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes). All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html GENERAL NOTES: " All code references to the International Residential Code shall be changed from 2003/2000 to 2006 or remove version reference: Inclusive Home Note #2/G1.1; Masonry Lap 1st note S1.0. FOUNDATION PLANS: 1. Show post base support by metal pedestal with 1" space above the floor (Detail 5/S1.1), R319.1.4 exception 1. Also, the CB series does not accept 16d nails. 2. Provide consistent brace wall holdowns on sheets S1.1 & S1.2, R602.10.6. The PAHD42 is rated less than required 1800 LBS when installed with end distance less than 8". The HPAHD22 is rated less than 1800 LBS when installed with end distance less than 8" and with fewer than 23 -16d nails. STRUCTURAL PLANS: 1. Show location and type of interior wall line bracing at intervals not exceeding 35' (50' exception) from exterior wall lines, R602.10.1.1. 2. Provide joist sizes and spacing in compliance with Table R802.4. 3. Show all brace wall connections from the foundation to the roof sheathing (BW-1 adjacent to double door, also below window opening W-11), R602.10.8. ELEVATIONS: 1. Show correct window notation for W-11 & w-12. 2. Provide an attic space ventilation calculation and specify size and location of all vents needed to comply, R806.2. 3. Revise the scupper size (Detail 4/A3.1) consistent with the required 6" size shown at Keynote #10, R903.4. 4. Note and specify appropriate (two-layer) underlayment material for the low-slope (2:12 to 4:12) asphalt shingle roof, R905.2.7. SECTIONS - DETAILS: 1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant (when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d. 2. Unvented attic space may not be used with Fiber Glass Shingle roof surfaces (Detail 3 & 7/S1.3). Show compliance with R806 by providing calculated venting or conditioned attic space (insulation underside of roof surface) with Tile or Built-up covering and no vapor retarders at the ceiling. 3. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing when eave venting is used, R806.3. This may be accomplished w/ baffles. PLUMBING PLANS: 1. Provide a plumbing design using a single code, 2006 UPC or 2006 IRC. UPC is referenced at notes 7 & 12/P1.1 & P1.2, although the fixture values are from the IRC. 2. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. The devices should conform to ASSE 1010-2004. Water hammer arresters are required for clothes washers, dishwashers and refrigerator water connections, UPC 609.10 or IRC P2903.5. 3. Revise the total developed length from meter to the most remote appliance on the system, UPC 1217.2, & Table 12-8 or IRC G2413.3 & Table G2413.4(1). An excessive distance of 102' is shown at two places on P1.2. 4. The gas line sections between the meter and second tee are undersized for the branch serving the 5 ton gas pack and cooktop. UPC 1217.2, & Table 12-8 IRC Table G2413.4(1). Increase these gas pipe sizes. MECHANICAL PLANS: 1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended). Revise Duct notation, M1.1. 2. Show dryer vent size and location for venting to exterior, M1501. 3. Provide return air duct size for the 2 ton gas pack, M1602. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN / 1000 BTU, M1403.1 (1 ton cooling = 12,000 BTU). 4. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements or Chapter 17, 2003 IRC. Show compliance for the water heater (utility closet door). Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2. ELECTRICAL PLANS: 1. Specify recessed lighting with 3" separation from combustibles or IC listing, R808, and compliance with energy efficiency leakage, N1102.4.3. Revise Note #1/E1.1. 2. Tucson Electric Power requires meters and associated equipment to be relocated from under patios when the service is upgraded, TEP SR-405.L. Relocate service. 3. Show the location of each device (Panel "B") on the Electrical Plan, E3305.1. 4. Show sub-panel 'A' feeder over-current protection (breaker size) for the #4 conductor ampacity or increase the conductor size to #3 (75 degree C), E3605.5. 5. Show receptacle outlets at wall spaces 2' or more (Family room wall at Pantry) so that no point along the wall (exclude door openings) is more than 6' from a receptacle outlet, E3801.2. 6. Hallways of 10' or more in length require a receptacle, E3801.10. 7. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3801.11. 8. Show all receptacle outlets in bathrooms (Jacuzzi #32) with ground fault circuit interrupting protection, E3802.1. 9. Indicate the location of all disconnect switches for air handling equipment (Gas Pack #2), E4001.5. OUTDOOR LIGHTING CODE 1. Revise the calculation (step 3) showing the correct acreage factor for determining the unshielded limit of 2,400 lumens. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Show consistent ceiling insulation values (Detail 3/S1.3 and Sections 1 & 2/A5.1), N1101.2. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/30/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |