| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. OCCUPANCY CALCULATIONS DOES NOT APPEAR CORRECT. SHOULD BE "B" FOR BUSINESS AT 1/100. REWORK. 2. CAN NOT SUPPORT PARTITIONS FROM CEILING GRID, MUST BE BRACED FROM STRUCTURE ABOVE. REWORK DETAIL 11/A2.0 |
| 05/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide mechanical plans (see details 1/M1.1 and 2/M1.1) with a legible background. Reference: Section 106.3.1, IMC 2006. |
| 05/16/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/16/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |