Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00508
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:Sears Financial corp 2:needs to show location/method of connection to public sewer 3:property does not front public sewer-needs wastewater 8th floor review of location/method of connection to public sewer 4:needs wastewater 8th floor review of easement/joint use sewer agreements if applicable |
| 02/20/2008 | DAVE MANN | FIRE | REVIEW | Denied | Confirm exit corridor and doors are rated. Indicate on plans. Also, (FYI) keynote 6 on Demo plan points to two different items. |
| 02/20/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/03/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0: DEMOLITION PLAN: KEYNOTE 6 ON GRID E. PLEASE REVIEW AND VERIFY LOCATION. 2. SHEET A1.0: DEMOLITION PLAN/REFLECTED CEILING PLAN/ROOF PLAN: REVIEW NOTE AT GRID C. THERE IS WORK IN THAT AREA ON THOSE PLANS. 3. SHEET A1.0: REFLECTED CEILING PLAN: SHOW SUPPORTS/DUCTWORK/OPENINGS/FRAMING ON ROOF PLAN. 4. DESIGN/DRAFT/DETAIL FRAMING WHEN MECHANICAL UNIT DOESN'T FALL DIRECTLY ON EXISTING JOIST. 5. SHEET 3 OF CALCULATIONS: VERIFY NEW MECHANICAL LOADS TO EXISTING JOISTS. 150 POUND LOAD ON JOIST IS NOT INDICATIVE OF ACTUAL LOADING. 6. SHEET A1.0: FLOOR PLAN: VERIFY ENLARGED REST ROOM PLAN IS 9/A2.0. 7. PROVIDE STRENGTH AND BRACING CALCULATIONS/DETAILS FOR INTERIOR PARTITIONS PER IBC 1607.13. 8. SHEET 6 OF CALCULATIONS: VERIFY NEW MECHANICAL LOADS TO EXISTING BEAMS. 550 POUND LOAD ON BEAM IS NOT INDICATIVE OF ACTUAL LOADING. 9. SHEETS A1.0/S2.1: COORDINATE LOCATION OF NEW MECHANICAL UNITS/OPENINGS. REVISE STRUCTURAL CALCULATIONS. 10. SHEET S2.1: ROOF FRAMING PLAN: VERIFY LOCATION OF NOTE 10. |
| 03/14/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 2. Indicate the maximum water temperature to be supplied to the public lavatories. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 3. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Section 1106.0, UPC 2006. |
| 03/17/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation for mercantile occupancy. Reference: Section 401.2, IMC 2006. 2. Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Section 403.2.1 (3), IMC 2006. 3. Show how the air supplied by HP-1 is to be returned from the exit corridor. Reference: Section 106.3.1, IMC 2006. 4. The 9" diameter duct from HP-2 serving the restrooms and janitor's room is penetrating a 1-hour fire partition. Provide a fire damper. Reference: Section 607, IMC 2006. 5. Provide fire dampers that comply with the rating requirements of Section 607.3.1, IMC 2006. |
| 03/18/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/01/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 04/01/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/01/2008 | GERARDO BONILLA | REJECT SHELF | Completed |