Permit Number: T08CM00508
Parcel: 117042890

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00508
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2008 GERRY KOZIOL WWM REVIEW Denied 1:Sears Financial corp
2:needs to show location/method of connection to public sewer
3:property does not front public sewer-needs wastewater 8th floor review of location/method of connection to public sewer
4:needs wastewater 8th floor review of easement/joint use sewer agreements if applicable
02/20/2008 DAVE MANN FIRE REVIEW Denied Confirm exit corridor and doors are rated. Indicate on plans.
Also, (FYI) keynote 6 on Demo plan points to two different items.
02/20/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/03/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0: DEMOLITION PLAN: KEYNOTE 6 ON GRID E. PLEASE REVIEW AND VERIFY LOCATION.
2. SHEET A1.0: DEMOLITION PLAN/REFLECTED CEILING PLAN/ROOF PLAN: REVIEW NOTE AT GRID C. THERE IS WORK IN THAT AREA ON THOSE PLANS.
3. SHEET A1.0: REFLECTED CEILING PLAN: SHOW SUPPORTS/DUCTWORK/OPENINGS/FRAMING ON ROOF PLAN.
4. DESIGN/DRAFT/DETAIL FRAMING WHEN MECHANICAL UNIT DOESN'T FALL DIRECTLY ON EXISTING JOIST.
5. SHEET 3 OF CALCULATIONS: VERIFY NEW MECHANICAL LOADS TO EXISTING JOISTS. 150 POUND LOAD ON JOIST IS NOT INDICATIVE OF ACTUAL LOADING.
6. SHEET A1.0: FLOOR PLAN: VERIFY ENLARGED REST ROOM PLAN IS 9/A2.0.
7. PROVIDE STRENGTH AND BRACING CALCULATIONS/DETAILS FOR INTERIOR PARTITIONS PER IBC 1607.13.
8. SHEET 6 OF CALCULATIONS: VERIFY NEW MECHANICAL LOADS TO EXISTING BEAMS. 550 POUND LOAD ON BEAM IS NOT INDICATIVE OF ACTUAL LOADING.
9. SHEETS A1.0/S2.1: COORDINATE LOCATION OF NEW MECHANICAL UNITS/OPENINGS. REVISE STRUCTURAL CALCULATIONS.
10. SHEET S2.1: ROOF FRAMING PLAN: VERIFY LOCATION OF NOTE 10.
03/14/2008 ROBERT SHERRY WATER REVIEW Approved
03/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
2. Indicate the maximum water temperature to be supplied to the public lavatories. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Section 1106.0, UPC 2006.
03/17/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation for mercantile occupancy. Reference: Section 401.2, IMC 2006.
2. Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Section 403.2.1 (3), IMC 2006.
3. Show how the air supplied by HP-1 is to be returned from the exit corridor. Reference: Section 106.3.1, IMC 2006.
4. The 9" diameter duct from HP-2 serving the restrooms and janitor's room is penetrating a 1-hour fire partition. Provide a fire damper. Reference: Section 607, IMC 2006.
5. Provide fire dampers that comply with the rating requirements of Section 607.3.1, IMC 2006.
03/18/2008 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2008 DELMA ROBEY APPROVAL SHELF Completed
04/01/2008 DELMA ROBEY OUT TO CUSTOMER Completed
04/01/2008 GERARDO BONILLA REJECT SHELF Completed