Permit Number: T08CM00505
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00505
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2008 TERRY STEVENS ZONING REVIEW Approved
02/14/2008 PAUL MACHADO ENGINEERING REVIEW Approved
02/14/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/14/2008 DAVE MANN FIRE REVIEW Approved
02/14/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/15/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/15/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM00505 2/15/08

1. Not known where "14400" came from.
2. Divisor of 277 would be only for one of the three phases. Provide service load calculations on a three phase basis.
3. Provide size of service entrance and service entrance conductors.
02/15/2008 ROBERT SHERRY WATER REVIEW Approved
02/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/15/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.