Permit Number: T08CM00501
Parcel: 10925013B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM00501
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00501 6/11/08

1. Account for electrical load on E-11. Circuit feeds receptacles.
2. Account for electrical load on E-34. Circuit feeds receptacles.
3. Account for electrical load on E-8. Circuit feeds one pole of HP-1.
06/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2008 CPIERCE1 OUT TO CUSTOMER Completed