Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM00501
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/11/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00501 6/11/08 1. Account for electrical load on E-11. Circuit feeds receptacles. 2. Account for electrical load on E-34. Circuit feeds receptacles. 3. Account for electrical load on E-8. Circuit feeds one pole of HP-1. |
| 06/12/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/24/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |