Permit Number: T08CM00501
Parcel: 10925013B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00501
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2008 HEATHER THRALL ZONING REVIEW Approved
02/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00501 2/14/08

1. Please indicate location of Panels C and D.
2. There is a note that New Panels C and D shall be series tested 65/10 KAIC. If this is because the original panels are rated that way please clarify this on the plans. Or, if these panels are actually new, they should not be shown as existing on the line diagram.
02/14/2008 ROBERT SHERRY WATER REVIEW Approved
02/14/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED CALCULATIONS AND DETAILS FOR ADDED ROOF TOP UNIT.
02/14/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/14/2008 PAUL MACHADO ENGINEERING REVIEW Approved
03/04/2008 CAGUILA1 FIRE REVIEW Needs Review
03/04/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review