Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00501
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 02/14/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00501 2/14/08 1. Please indicate location of Panels C and D. 2. There is a note that New Panels C and D shall be series tested 65/10 KAIC. If this is because the original panels are rated that way please clarify this on the plans. Or, if these panels are actually new, they should not be shown as existing on the line diagram. |
| 02/14/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/14/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED CALCULATIONS AND DETAILS FOR ADDED ROOF TOP UNIT. |
| 02/14/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 02/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/14/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 03/04/2008 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 03/04/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |