Permit Number - T08CM00491
Review Name: OTHER
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2008 ANY PLUMBING-COMMERCIAL REVIEW Active
02/13/2008 ANY MECHANICAL-COMMERCIAL REVIEW Active
02/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00491 2/14/08

1. Provide electrical design, including but not limited to conduit and conductor size and type, panel and circuit number, panel schedule, load calculations, ground fault, short circuit, and overload protection, equipment disconnecting means.
2. 1/8" minimum font size.
3. Add Structural to WorkFlow.