Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/13/2008 | ANY | PLUMBING-COMMERCIAL | REVIEW | Active | |
02/13/2008 | ANY | MECHANICAL-COMMERCIAL | REVIEW | Active | |
02/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00491 2/14/08 1. Provide electrical design, including but not limited to conduit and conductor size and type, panel and circuit number, panel schedule, load calculations, ground fault, short circuit, and overload protection, equipment disconnecting means. 2. 1/8" minimum font size. 3. Add Structural to WorkFlow. |