Permit Number: T08CM00484
Parcel: 13323164A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00484
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. INCORPORATE NEW FITTING ROOM CUTSHEET INFORMATION (PLANS, PERTINENT DETAILS) ONTO SUBMITTAL DRAWING SET.
05/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. A 3/32" font may be allowed with an appeal to the building official. http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/Petition_of_Appeal.pdf
2. Exhaust fan EF-11 shall operate whenever air is being supplied to the restroom (i.e. during all hours of store operation), not just when the restroom is being occupied. Reference: Section 403.2.1, IMC 2006.
3. Correct the label for the TLE exhaust fan EF8 on sheet MAC1. Reference: Section 106.3.1, IMC 2006
05/13/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A 3/32" font may be allowed with an appeal to the building official. http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/Petition_of_Appeal.pdf
2. The waste and vent isometric for the temporary vision center shows a simplex lift station for the two sinks. A lift station in a public use situation requires either a duplex system or an appeal to the building official if a simplex system is to be used. Reference: Section 710.9, UPC 2006.
3. Provide a check valve and a full-way gate or ball valve for the discharge of the lift station. Reference: Section 710.4, UPC 2006.
4. Show where and how the discharge of the lift station is to be connecting to the building drain. Provide information to demonstrate that the connection point is adequately sized. Reference: Sections 710.5 and 805.0, UPC 2006.
5. Provide an audible and visual alarm for the lift station per Section 710.9, UPC 2006.
6. Indicate the size of the tailpiece used for FS-1 in the combination waste and vent system for the refrigerated cases (4/P1). The Floor/Roof Drain Schedule (P3) does not clearly indicate the tailpiece size for the floor sink FS1. The specified model numbers for both the Josam and Sioux Chief floor sinks are not shown in their respective on-line catalogs and the Oatey catalog indicates that the model 42722 floor sink has a 4" tailpiece. Reference: Section 910.4, UPC 2006.
7. Specify the type of backflow preventer to be used for the connection of the Pharmate RO System. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. (2/MPH1)
05/16/2008 TERRY STEVENS ZONING REVIEW Approved
05/27/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Compile complete sets for final approval and signature.
2. It appears that the compressor assembly is aprox. 50' from MSWB, not 150'. Please rework fault calculations and provide fault current rating of equipment.
3. Add Existing Panel HR to HB Panel Schedule electrical load.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2008 VFLORES1 OUT TO CUSTOMER Completed
06/12/2008 SHANAE POWELL REJECT SHELF Completed