Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM00484
Parcel: 13323164A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00484
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2008 DAVE MANN FIRE REVIEW Approved
02/22/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. 20% OF CONSTRUCTION COSTS MUST BE PROVIDED FOR ACCESSIBILITY; IBC 2006 SECTIONS 3906.6 AND 3906.7. SHOW COST BREAKDOWN
2. PROVIDE APPROVED BUILDING OFFICAL APPEAL FOR USE OF 3/32" LETTERING FONT SIZE
3. PROVIDE DETAILED ARCHITECTURAL SITE SITE PLAN SHOWING ALL ACCESSIBLE ROUTES FROM PUBLIC R.O.W., PARKING AND EGRESS TO BUILDING. PROVIDE SPOT ELEVATIONS SHOWING COMPLIANCE WITH ACCESSIBLE ROUTE SLOPE COMPLIANCE
4. DOOR HARDWARE SCHEDULE NOT PROVIDED
SHEET A1
5. DESIGN AND DETAIL ALL NEW FITTING ROOMS, PROVIDE STRUCTURAL CALCULATIONS AND ALL ACCESSIBLE COMPLIANCE
SHEET A3
6. DESIGN AND DETAIL PHOTO LAB AND SHOW ACCESSIBILITY COMPLIANCE
7. COURTESY DESK TO HAVE A 3' WIDE ACCESSIBLE AREA IN COUNTER TOP
SHEET A-4
8. DEFINE HEIGHT OF STORAGE BINS. IF STORAGE IS 12' AND HIGHER, SHOW COMPLIANCE WITH HI PILE STORAGE CODE REQUIREMENTS.
9. PROVIDE STRUCTURAL CALCULATIONS FOR STORAGE SHELVING ANCHORING
10. DOOR NOS. 162C AND 162B ARE NOT ON DOOR SCHEDULE AND ARE REQUIRED TO BE FIRE RATED
11. SECURITY ROOM DOOR NEEDS SPECIAL RELEASE HARDWARE IN CASE OF FIRE
SHEET A-5
12. CLARIFY HEIGHT OF STORAGE, IF ABOVE 12' SHOW COMPLIANCE WITH HIGH PILE STORAGE CODE REQUIREMENTS
13. PROVIDE STRUCTURAL CALCULATIONS FOR RACK ANCHORING
SHEET A-6
14. PROVIDE STRUCTURAL CALCULATIONS FOR MG21 WASTE OIL TANK MOUNTING
SHEET AC1
15. SHOW DETAIL OF ACCESSIBLE END OF COUNTER
16. SHOW TOILET ELEVATIONS FOR ACCESSORY ACCESSIBLE COMPLIANCE HEIGHTS AND DIMENSIONS
SHEET PH1, PH2 AND PH3
17. PROVIDE ALL TOILET ELEVATIONS
18. PROVIDE STRUCTURAL DETAILING AND CALCULATIONS FOR BOTH ROLLING GRILLS
19. WATER CLOSET CENTER LINE MAXIMUM 18" FROM WALL
SHEET S1
20. SUPPORT FRAME FOR MECHANICAL UNITS ON ROOF SHOWN LOCATED ON WRONG SIDE OF COLUMN CENTER LINE 7. REFERENCE DETAILS 7/A5, 6/P1, 2/R2 AND 2/RE1
02/22/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 21. SHEET S1: GENERAL NOTE 4.1 STATES ALLOWABLE SOIL BEARING PRESSURE OF 3200 PSF. WHERE IS GEOTECHNICAL REPORT? PRESUMPTIVE SOIL BEARING IS 1000 PSF AT 12" BELOW GRADE OR 1500 PSF AT 18" BELOW GRADE (AMENDMENT SECTION 1805.2)
03/04/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide a disconnecting means for EF-3 and EF-12, or justify otherwise. Please note that EF-3 and EF-12 are not on the Fan Schedule Sheet M3. Typical for all instances which may apply.
2. Note on Detail 2 Sheet refers to 8-E3.1. No such reference on E3.1.
3. Please add the following note to Sheet EVC1: "All work in patient care areas shall be done according to NEC 517.13. "
4. Provide a disconnecting means for the water heater in the Vision Care Center. Typical for all such instances which may apply.
5. Phase B on Panel LD is overloaded at 35A. Note that demand factor may not be taken for receptacle loads because total of such loads is less than 10K. Reference NEC 220.44.
6. Phases A and B on Panel LD2 are overloaded at 155A and 182A.
7. Could not locate Panel LD2, or Transformer TD2 on the plans. Plans Examiner to check for compliance with NEC 240.21.
8. Provide overcurrent protection for Busways BL1A and BL1B. Reference NEC 368.17 (A).
9. Detail 4 on Sheet E3.1 provides for ceiling mounting of transformer. Dry Type Transformer Schedule Sheet E4 specifies a floor mount for TD2. Please clarify.
10. Compressor Assembly needs further definition. Please provide sufficient detail/information to allow Plans Examiner to verify National Electrical Code compliance. If this is a listed assembly, a submittal of the cut sheet with all pertinent electrical parameters may suffice. Willing to discuss.
11. Provide available fault current at Compressor Assembly, and fault current rating of this equipment.
12. Demonstrate that Panel HB is not overloaded.
13. All three phases on Panel LY exceed the 50A CB. Check the feeder too, for this instance and all others which may apply.
14. Utility transformer is 208/120V secondary on the One-Line Diagram, but the service is 480/277V. Please clarify.
15. On Sheet E2.1, there is a reference to Detail 8 on Sheet E3.1. There is no Detail 8 on Sheet E3.1. Please clarify.
16. Clarify the nature of the Paint Booths powered on Circuits LD2-15,17,19 and 21. Plans Examiner to evaluate per NEC Article 516. Suggest you call to discuss Just a paint station, per Mo Lisa Garcia, 913.742.5578, 4/15/08. (Was instructed to get MSDS sheets and provide letter from Owner documenting nature of paints being mixed, and to consider Classified Location in the case where flammable vapors are involved.)
03/07/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006.
2. Clarify how the sequence of operation for the restroom exhaust (EF-11) will prevent complete recirculation of the air from the restroom. Reference: Section 403.2.1, IMC 2006.
3. Provide equipment data for EF-7. Clarify the purpose of EF-7, e.g. ventilation for TLE pit per Section 502.15, IMC 2006. Reference: Section 106.3.1, IMC 2006.
03/07/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006.
2. Provide water isometrics and waste and vent isometrics for the temporary vision center. Reference: Section 103.2.3, UPC 2006.
3. Provide information to show that the specified emergency eyewashes (in TLE/TLE pit) will have adequate water pressure for proper operation. Reference: Sections 103.2.3, 608.1, UPC 2006.
4. Detail 6/P1 references keynote 15.400; where is this keynote explained?
5. Revise the vent sizes for the combination waste and vent system for the refrigerated cases (4/P1) to comply with the requirements of Section 910.3, UPC 2006.
6. Indicate the size of the tailpiece used for FS-1 in the combination waste and vent system for the refrigerated cases (4/P1). Reference: Section 910.4, UPC 2006.
7. Provide an accessible cleanout in each vent in the combination waste and vent system for the refrigerated cases (4/P1). Reference: Section 910.6, UPC 2006.
8. Appliances (e.g. Pharmate RO System) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
9. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
03/07/2008 ROBERT SHERRY WATER REVIEW Approved
03/14/2008 GERRY KOZIOL WWM REVIEW Approved
03/17/2008 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM00484
7150 E. Speedway Blvd.
TI: Walmart

TRANSMITTAL DATE: 3/17/08

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Per determination by the Zoning Administrator and research of DSD records and aerial photos, an area within the parking lot was approved for a Temporary Use Permit for a garden center. The TUP expired on January 5, 2005. The area in question is still being used as a garden center as of this review.

A review of the aerial photos show multiple storage containers located in the southeast corner of the property. These do not appear to have been permitted.

2. Additional permits for the Tenant Improvement cannot be issued until permits have been secured for the above mentioned garden center and storage containers or the garden center and storage containers are removed from this site.

3. Provide documentation of the required permits or verification that the violations have been removed.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM00484.doc

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
04/30/2008 SHANAE POWELL REJECT SHELF Completed