Permit Number: T08CM00457
Parcel: 110055340

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00457
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2008 STEVE SHIELDS ZONING REVIEW Approved
02/11/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2006.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
02/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/11/2008 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing water meter and reduced pressure backflow preventer.
02/11/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PRIVATE BATH MUST BE ADA ADAPTABLE.
2. ALL COUNTER MOUNTED SINKS TO BE ACCESSIBLE AT 2'-10" AFF.
3. DRINKING FOUNTAIN TO BE HIGH/LOW.
02/11/2008 LOREN MAKUS ENGINEERING REVIEW Approved
02/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water and waste & vent riser diagrams.
2. Provide listing and installation information for the steam generaor and for the tankless water heater.
3. Provide information to show that the existing water service and meter are adequate to accomodate the new plumbing fixtures.
4. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
02/11/2008 DAVE MANN FIRE REVIEW Approved
02/11/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/19/2008 CPIERCE1 WWM REVIEW Needs Review