Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00437
Parcel: 137055110

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM00437
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/23/2008 TERRY STEVENS ZONING REVIEW Denied Provide revised plans for the vehicular use area to the east of major 5 & 6 between the north side of shops 6 and the south side of minor 4. It appears the trash enclosures and loading zones have been changed. Clearly indicate maneuverability for loading zones and trash enclosures as well as PAAL widths. The apporved plans indicate 5 loading zones in this area the submitted plans indicate 4. Clarify.
05/23/2008 MARTIN BROWN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
05/30/2008 ROBERT SHERRY WATER REVIEW Denied Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project.
06/05/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2008 DELMA ROBEY APPROVAL SHELF Completed
06/10/2008 DELMA ROBEY OUT TO CUSTOMER Completed
06/10/2008 GERARDO BONILLA REJECT SHELF Completed