Permit Number: T08CM00406
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00406
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2008 STEVE SHIELDS ZONING REVIEW Approved
02/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the sequence of operation for EF-1 to show how recirculation of the air supplied to the restrooms will be avoided.
2. Provide information to show how the contractor can comply with note 14, sheet M-2
02/06/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/06/2008 ROBERT SHERRY WATER REVIEW Approved
02/06/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. HIGH/LOW DRINKING FOUNTAIN REQUIRED PER IBC 2006.
02/06/2008 LOREN MAKUS ENGINEERING REVIEW Approved
02/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagrams for the waste and vent piping. 2. Clarify what is existing and what is new.
02/06/2008 MARTIN BROWN FIRE REVIEW Approved
02/06/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/08/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2008 GERARDO BONILLA OUT TO CUSTOMER Completed