Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00406
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/06/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
02/06/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the sequence of operation for EF-1 to show how recirculation of the air supplied to the restrooms will be avoided. 2. Provide information to show how the contractor can comply with note 14, sheet M-2 |
02/06/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/06/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/06/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. HIGH/LOW DRINKING FOUNTAIN REQUIRED PER IBC 2006. |
02/06/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
02/06/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagrams for the waste and vent piping. 2. Clarify what is existing and what is new. |
02/06/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/06/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/08/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/08/2008 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |