Permit Number: T08CM00405
Parcel: 13323190A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM00405
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2008 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM00405
7760 E. Speedway Blvd.
Site Plan

TRANSMITTAL DATE: 8/15/08

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.2 Provide the legal description of the parcel being developed. The lot split (reconfiguration) must be approved by the City of Tucson and completed before approval of this site plan.

Provide on the site plan, the case number of the lot split in the lower right corner near the title block.

Change the line weight of the boundaries of lot #6 to a lighter weight and clearly indicate the new lot lines with a heavier line weight for clarity purposes.

2. The parallel parking spaces located along the south property line are required to be a minimum length of 23'. Revise. This area is "clouded" but has no detail call out or detail.

3. DS 2-02.2.2.A.6 Provide the percentage of building area expansion. The expansion calculations required are cumulative for all previous expansions as well as this expansion. Expansion calculations have been provided for only this project and do not appear to include previous expansions for the rest of the shopping center.

4. DS 2-02.2.1.11 The 24' PAAL located along the west side of the proposed buildings is required to have a 2' minimum clearance along the west side of the PAAL. See DS 3-05.2.2.B.3. A Development Standards Modification Request (DSMR), which zoning is willing to support, can be applied for to change the required 2' clearance to 0'.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM00405-2.doc
08/15/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/26/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. A street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. On streets designated as Major Streets and Routes (MS&R), the street landscape border is measured from the MS&R right-of-way line as determined by LUC 2.8.3.4. Revise plans accordingly. NOTE: Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee, up to five (5) feet of the required ten (10) foot width be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. If providing up to five-foot of the required 10-foot street landscape border within the MS&R right-of-way, provide documentation indicating approval. LUC 3.7.2.4.A.3

2. Screens may be located within the street landscape border, if the following criteria are met: The street landscape border is a minimum of ten (10) feet wide; and screen walls constructed in a single continuous line shall extend into a street landscape border no more than the actual width of the fence or wall. Where a wall incorporates offsets or similar design features, a screen may extend a maximum of three (3) feet into the street landscape border.
Revise screen wall location to meet code. LUC 3.7.3.2.C
09/10/2008 JASON GREEN ENGINEERING REVIEW Denied DATE: September 10, 2008
SUBJECT: 7760 E Speedway Blvd Site Plan- 3rd Engineering Review
TO: Olsson Associates Attn: Richard G. Macias, P.E.
LOCATION: T14S R15E Sec08 Ward 2
REVIEWERS: Jason Green, CFM
ACTIVITY: T08CM00405 (Site Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan (T08CM00405) (Drainage Statement (Olsson Associates, 28JAN08) that was submitted on the 1st review was not included with the 2nd or 3rd submittal, provide all information that is associated with the design of this project) for the above referenced property. Engineering Division does not recommend approval of the site plan application at this time. The following items need to be addressed:

SITE PLAN COMMENTS:

1) Complied
2) Restated: DS Sec.2-02.2.1.A.5: Provide the recordation information with the COT approved lot reconfiguration for the subject parcel. The Zoning Department prior to site plan approval must approve all lot reconfiguration. The lot combination must be approved prior to site plan approval.
3) Complied
4) Complied
5) Complied
6) Restated: DS Sec.2-02.1.A.8: Revise the 24-foot PAAL located along the west side of the proposed buildings. Per DS Sec.3-05.2.2.B.3 a minimum distance of 2-feet (26-feet total PAAL width) must be maintained between a PAAL and any wall, screen or other obstruction. A Development Standards Modification Request (DSMR) is required to eliminateor change the required 2' clearance to 0'.
7) Complied
8) Complied
9) Complied
10) Complied
11) Complied
12) Acknowledged
13) Complied
14) Acknowledged
15) Ackowledged

GENERAL COMMENTS:

Please provide a revised site plan and the Drainage Statement that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package. The site plan will not be approved if the supplemental information (Drainage Statement) is not included with the resubmittal.

Further comments may be generated upon resubmittal of the site plan review.

If you have any questions or to schedule an appointment I can be reached at 837-4929.

Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
09/16/2008 SUE REEVES REJECT SHELF Completed