Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM00389
Parcel: 13317066A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00389
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/03/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/03/2008 CAGUILA1 WWM REVIEW Needs Review
03/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00389 3/3/08

1. Add a note in a prominent place on the plans: "Wiring in all patient care areas shall comply with the requirements of NEC 517.13. This effects new and existing circuits and devices."
2. Provide an electrical circuit for the fan coil on the current revision. Note that its electrical requirements are for 230V power, but the panel schedule is apparently 208V.
3. Panel schedule calls it a 280V panel. Load calculations are based on 208V line-to-line.