Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/03/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/03/2008 CAGUILA1 WWM REVIEW Needs Review
03/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00389 3/3/08

1. Add a note in a prominent place on the plans: "Wiring in all patient care areas shall comply with the requirements of NEC 517.13. This effects new and existing circuits and devices."
2. Provide an electrical circuit for the fan coil on the current revision. Note that its electrical requirements are for 230V power, but the panel schedule is apparently 208V.
3. Panel schedule calls it a 280V panel. Load calculations are based on 208V line-to-line.