Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00389
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/03/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
03/03/2008 | CAGUILA1 | WWM | REVIEW | Needs Review | |
03/03/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00389 3/3/08 1. Add a note in a prominent place on the plans: "Wiring in all patient care areas shall comply with the requirements of NEC 517.13. This effects new and existing circuits and devices." 2. Provide an electrical circuit for the fan coil on the current revision. Note that its electrical requirements are for 230V power, but the panel schedule is apparently 208V. 3. Panel schedule calls it a 280V panel. Load calculations are based on 208V line-to-line. |