| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00388 5/8/08 1. Provide overload protection for EH-1 and EH-2. NEC 430 Part III. COMMENT MADE ON SUBMITTAL OF 2/5/08. This 8.3 A unit is not protected by a 30A circuit breaker. 2. Provide Ground Fault and Short Circuit protection for EH-1 and EH-2. NEC 430 Part V. COMMENT MADE ON SUBMITTAL OF 2/5/08. This 8.3 A unit is not protected by a 30A circuit breaker. 3. Electric Unit Heater Schedule Sheet M-1 specifies 2 unit heaters. Electrical provides power for just one. Please clarify. |