Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
05/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00388 5/8/08

1. Provide overload protection for EH-1 and EH-2. NEC 430 Part III. COMMENT MADE ON SUBMITTAL OF 2/5/08. This 8.3 A unit is not protected by a 30A circuit breaker.
2. Provide Ground Fault and Short Circuit protection for EH-1 and EH-2. NEC 430 Part V. COMMENT MADE ON SUBMITTAL OF 2/5/08. This 8.3 A unit is not protected by a 30A circuit breaker.
3. Electric Unit Heater Schedule Sheet M-1 specifies 2 unit heaters. Electrical provides power for just one. Please clarify.