Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00388
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 02/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the listing information for the hood. 2. Show how the make up air for the kitchen complies with Section 508, IMC 2006. 3. Revise the outside air calculations per Section 403.3, IMC 2006. 4. Show how the hood exhaust system will comply with Section 507.2.1.1, IMC 2006. |
| 02/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00388 2/5/08 1. Provide overload protection for EH-1 and EH-2. NEC 430 Part III. 2. Provide Ground Fault and Short Circuit protection for EH-1 and EH-2. NEC 430 Part V. 3. Provide Panel Schedule P, and demonstrate that no phase is being overloaded. |
| 02/05/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/05/2008 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED STRUCTURAL CALS AND DETAILS FOR ROOF TOP MOUNTED MECHANICAL EXHAUST SYSTEM SUPPORT 2. NEED VALUATION |
| 02/05/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a riser diagram for the installation of the 3-compartment sink. 2. Provide a design for the gas service to the building. 3. Show the water service to the building, including the size of the water meter and the backflow preventer. |
| 02/05/2008 | MARTIN BROWN | FIRE | REVIEW | Approved |