Permit Number: T08CM00388
Parcel: 12911052A

Address:
1050 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00388
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2008 HEATHER THRALL ZONING REVIEW Approved
02/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the listing information for the hood.
2. Show how the make up air for the kitchen complies with Section 508, IMC 2006.
3. Revise the outside air calculations per Section 403.3, IMC 2006.
4. Show how the hood exhaust system will comply with Section 507.2.1.1, IMC 2006.
02/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00388 2/5/08

1. Provide overload protection for EH-1 and EH-2. NEC 430 Part III.
2. Provide Ground Fault and Short Circuit protection for EH-1 and EH-2. NEC 430 Part V.
3. Provide Panel Schedule P, and demonstrate that no phase is being overloaded.
02/05/2008 JASON GREEN ENGINEERING REVIEW Approved
02/05/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. NEED STRUCTURAL CALS AND DETAILS FOR ROOF TOP MOUNTED MECHANICAL EXHAUST SYSTEM SUPPORT
2. NEED VALUATION
02/05/2008 ROBERT SHERRY WATER REVIEW Approved
02/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the installation of the 3-compartment sink.
2. Provide a design for the gas service to the building.
3. Show the water service to the building, including the size of the water meter and the backflow preventer.
02/05/2008 MARTIN BROWN FIRE REVIEW Approved