Permit Number: T08CM00386
Parcel: 11807237F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00386
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/15/2008 GBONILL1 WWM REVIEW Needs Review
02/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/15/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/15/2008 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/15/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Provide a sequence of operation to show how supply air to the restroom will not be recirculated (i.e. will the exhaust fan always be running at the same time as the a/c/ unit is running). Reference Section 403.2.1, IMC 2006.