Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00386
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 02/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the mechanical plan with the architectural plans. If substantial changes are to be made to the inlet and outlet locations, provide the duct layouts. 2. Provide a sequence of operation to show how supply air to the restroom will not be recirculated. Reference Section 403.2.1, IMC 2006. |
| 02/05/2008 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/05/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/05/2008 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE DETAILED SITE PLAN SHOWING ACCESSIBLE ROUTES FROM PUBLIC TRANSPORATTION TO FRONT DOOR AND ACCESSIBLE PARKING TO FRONT DOOR WITH APPLICABLE SPOT GRADES SHOWING SLOPES OF ROUTES. 2. PROVIDE ACCESSIBLE PUBLIC TOILET, REDESIGN TO MEET 2006IBC AND ANSI 117.1 |
| 02/05/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 02/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the water temperature to the lavatory is to be controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Show how the hand sink located near the new floor sink will be drained. |
| 02/05/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/05/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/05/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |