Permit Number: T08CM00386
Parcel: 11807237F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00386
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2008 HEATHER THRALL ZONING REVIEW Approved
02/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the mechanical plan with the architectural plans. If substantial changes are to be made to the inlet and outlet locations, provide the duct layouts.
2. Provide a sequence of operation to show how supply air to the restroom will not be recirculated. Reference Section 403.2.1, IMC 2006.
02/05/2008 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/05/2008 ROBERT SHERRY WATER REVIEW Approved
02/05/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE DETAILED SITE PLAN SHOWING ACCESSIBLE ROUTES FROM PUBLIC TRANSPORATTION TO FRONT DOOR AND ACCESSIBLE PARKING TO FRONT DOOR WITH APPLICABLE SPOT GRADES SHOWING SLOPES OF ROUTES.
2. PROVIDE ACCESSIBLE PUBLIC TOILET, REDESIGN TO MEET 2006IBC AND ANSI 117.1
02/05/2008 CPIERCE1 WWM REVIEW Needs Review
02/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the water temperature to the lavatory is to be controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Show how the hand sink located near the new floor sink will be drained.
02/05/2008 JASON GREEN ENGINEERING REVIEW Approved
02/05/2008 MARTIN BROWN FIRE REVIEW Approved
02/05/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review