Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00385
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2008 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the local exhaust is provided for the nail station tables. Reference footnote (i), Table 403.3, IMC 2006. 2. If the pedicures are used for the application of nail polish, provide local exhaust. Reference footnote (i), Table 403.3, IMC 2006. |
| 02/05/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the water heater pan drain to ¾" minimum. Reference Section 508.4, UPC 2006 2. Show how drainage is to be provided for the reduced pressure backflow preventers. |
| 02/05/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00385 2/5/08 1. Fixed storage water heater is to be considered a continuous load. Reference NEC 422.13. Please factor that into panel load calculations. It appears that the panel is overloaded. 2. It appears that the 40A circuit feeding the transformer primary is overloaded. Please note that the transformer also is overloaded. 3. It appears that the electrical load on Circuit 2 is 1053 VA, not 255. |
| 02/05/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/05/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 02/08/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 02/08/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |