Permit Number: T08CM00385
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00385
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2008 HEATHER THRALL ZONING REVIEW Approved
02/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the local exhaust is provided for the nail station tables. Reference footnote (i), Table 403.3, IMC 2006.
2. If the pedicures are used for the application of nail polish, provide local exhaust. Reference footnote (i), Table 403.3, IMC 2006.
02/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00385 2/5/08

1. Fixed storage water heater is to be considered a continuous load. Reference NEC 422.13. Please factor that into panel load calculations. It appears that the panel is overloaded.
2. It appears that the 40A circuit feeding the transformer primary is overloaded. Please note that the transformer also is overloaded.
3. It appears that the electrical load on Circuit 2 is 1053 VA, not 255.
02/05/2008 ROBERT SHERRY WATER REVIEW Approved
02/05/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
02/05/2008 JASON GREEN ENGINEERING REVIEW Approved
02/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the water heater pan drain to ¾" minimum. Reference Section 508.4, UPC 2006
2. Show how drainage is to be provided for the reduced pressure backflow preventers.
02/05/2008 MARTIN BROWN FIRE REVIEW Approved
02/08/2008 GBONILL1 WWM REVIEW Needs Review
02/08/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed